Emergency
Emergency Exit Inspection Checklist: Routes, Doors, Signs
- Frequency
- Monthly
- Completed by
- Supervisor, fire warden or safety officer
- Approved by
- Facility manager
- The checklist
- 25 checks · 5 sections
An emergency exit inspection checklist is the walk-through check of one exit route from the work area to the outside: the route is clear and wide enough, the signs and emergency lighting work, the door opens from the inside without a key, and nothing blocks the path outside. A supervisor, fire warden or safety officer can complete it. A locked or blocked exit is fixed on the spot or reported straight away.
No regulation cited here sets an inspection interval, because the duty is continuous. In the United States, OSHA 29 CFR 1910.37 requires exit routes to be free and unobstructed and their safeguards to be in working order at all times, and 1910.36(d) requires exit doors to open from the inside without keys, tools or special knowledge. In Türkiye, Annex 1 of the Regulation on Health and Safety Measures in Workplace Buildings requires emergency exit doors to open outward and never be locked or fastened, and the Regulation on the Fire Protection of Buildings sets the door, sign and emergency lighting rules. In England and Wales, article 14 of the Regulatory Reform (Fire Safety) Order 2005 requires routes and exits to be kept clear at all times. This form uses a monthly check as a practical interval; walk the routes more often where stock, deliveries or waste tend to collect in them.
The checklist does not replace the periodic testing and maintenance of emergency lighting and fire doors by a competent contractor, or a fire risk assessment. To decide how many exits you need and where, see our fire risk assessment guide; for who does what during an evacuation, see the emergency action plan guide.
How to use this checklist
- Fill one form per exit route. Start in the work area and walk the route all the way to the outside, as people would in an evacuation.
- Check the route first, then the signs, then the door, and finish by going through the door and checking the path outside.
- Open every door on the route yourself, from the inside, without a key. Press the test button on emergency lights and lit exit signs where there is one.
- Mark each check Pass, Fail or N/A and photograph every defect.
- Remove obstructions and unlock doors before you leave the exit. If a critical check fails and you cannot fix it, tell the responsible manager immediately.
- Sign the form and keep it with the fire safety records.
The checklist: Emergency Exit Inspection Checklist: Routes, Doors, Signs
Inspection details
Route to the exit
- 1.
The route is clear along its whole length: no stock, pallets, equipment, furniture or wasteCritical
Temporary storage counts too: a route must be clear even if the items will be moved later.
PassFailN/A - 2.
Nothing narrows the route below its minimum width
US: exit access at least 28 in (71.1 cm) at all points. Türkiye: escape corridors at least 110 cm; no exit or escape stair narrower than 80 cm.
PassFailN/A - 3.
Nothing hangs or projects into the route at head height
US: no projection from the ceiling lower than 6 ft 8 in (2.0 m) above the floor. Türkiye: escape corridor height at least 210 cm.
PassFailN/A - 4.
No highly flammable materials, furnishings or decorations are kept on the route
Ref.: [4]
PassFailN/A - 5.
The route does not pass through a room that can be locked
Check again after any change of layout, such as new partitions or a storeroom built across a corridor.
Ref.: [4]
PassFailN/A - 6.PassFailN/A
- 7.
The emergency lights on the route come on when tested
Press the test button or use the test switch. This is a function check only; the duration test belongs to periodic maintenance. Türkiye: at least 60 minutes, 120 where the user load is over 200.
PassFailN/A
Exit signs
- 8.
The exit is marked with an exit sign that is in place and undamaged
US: the word Exit in letters at least 6 in (15.2 cm) high. Türkiye: white on green, at least 15 cm high, mounted 200 to 240 cm above the floor.
PassFailN/A - 9.PassFailN/A
- 10.PassFailN/A
- 11.PassFailN/A
- 12.
Doors on the route that could be mistaken for the exit are marked with what they are
US: marked Not an Exit or with the actual use, such as Closet.
PassFailN/A
Exit door
- 13.
The door opens from the inside without a key, tool or code; there is no padlock, chain or bolt on itCritical
PassFailN/A - 14.
The door opens fully and easily by hand, and the panic bar or handle worksCritical
Open it yourself. A door that sticks, drags on the floor or needs a hard push fails. Türkiye: opening force not over 110 N.
PassFailN/A - 15.
The door opens in the direction of escape
Türkiye: workplace emergency exit doors open outward. US: required where the room holds more than 50 people or is a high hazard area.
PassFailN/A - 16.PassFailN/A
- 17.
A door alarm or access-control device does not stop the door from being openedCritical
Mark N/A if the door has no such device.
PassFailN/A - 18.
Fire doors on the route close fully by themselves and are not wedged or tied open
Open the door fully and let go: it should close and latch. Mark N/A if the route has no fire doors.
PassFailN/A
Outside the exit
- 19.
Nothing blocks the outside of the door: no vehicles, pallets, bins or stored materialsCritical
Go through the door and look. A door that opens from the inside can still be blocked from the outside.
PassFailN/A - 20.
From the door, the way is open to a street, walkway or open space away from the buildingCritical
A locked yard gate or a fenced dead end fails this check.
PassFailN/A - 21.
Outdoor stairs and walkways on the route have guardrails on open sides and are free of snow, ice and loose surfaces
Mark N/A if the route has no outdoor part.
Ref.: [3]
PassFailN/A
Result
Critical check: if it fails, stop and correct it before work continues.
Sign-off
Inspector
Facility manager
Run this checklist on your phone
FindRisk turns inspections into a few taps: AI-generated checklists you can edit and save as templates, photo markup with AI hazard analysis, Fine-Kinney risk scoring and an instant PDF report.
Download FindRiskLegal basis and references
- [1] Türkiye: İşyeri Bina ve Eklentilerinde Alınacak Sağlık ve Güvenlik Önlemlerine İlişkin Yönetmelik (Resmî Gazete, 17.07.2013, 28710) — Annex 1, item 10 (escape routes and emergency exits: open to the outside or a safe area, unobstructed, doors open outward, no sliding or revolving doors, not locked or fastened, signs, emergency lighting) and item 35(e) (doors on escape routes open from the inside at all times).
- [2] Türkiye: Binaların Yangından Korunması Hakkında Yönetmelik (Resmî Gazete, 19.12.2007, 26735) — Article 30 (no locks or bolts that prevent escape; exits clearly visible), Article 31 (escape route defined as continuous and unobstructed), Article 33 (widths, corridor height, exits kept unobstructed), Article 47 (escape route doors), Articles 70 to 73 (emergency lighting and direction signs) and Article 84 (periodic control, testing and maintenance under the relevant standards).
- [3] United States: OSHA 29 CFR 1910.36, Design and construction requirements for exit routes — (a)(3) self-closing fire doors; (c) exit discharge; (d) unlocked exit doors and door devices; (e) door swing; (g) minimum height and width; (h) outdoor exit routes.
- [4] United States: OSHA 29 CFR 1910.37, Maintenance, safeguards, and operational features for exit routes — (a)(1) no highly flammable furnishings; (a)(3) free and unobstructed routes, no lockable rooms; (a)(4) safeguards in working order at all times; (b)(1) to (b)(7) lighting and exit signs.
- [5] United Kingdom: The Regulatory Reform (Fire Safety) Order 2005 (S.I. 2005/1541) — Applies in England and Wales. Article 14 (emergency routes and exits kept clear at all times; doors, signs and emergency lighting) and article 17 (maintenance).
Version 1 · Updated November 20, 2026 · findrisk.net/checklists/emergency-exit-inspection-checklist/
Fill in this checklist on your phone. Scan to download FindRisk: run the checklist, add photos, score risks and share a PDF report in minutes.
Version 1 · Updated November 20, 2026 · findrisk.net/checklists/emergency-exit-inspection-checklist/
Frequently asked questions
How often should emergency exits be inspected?
The rules set a continuous duty, not an interval. OSHA 1910.37(a) requires exit routes to be free and unobstructed and their safeguards to be in proper working order at all times, and article 14 of the UK Fire Safety Order requires routes and exits to be kept clear at all times. A documented monthly check is a practical way to show this, with a quick look every day in areas where goods or waste pile up.
Can an emergency exit door be locked?
Not in a way that stops people getting out. OSHA 1910.36(d)(1) requires that employees can open an exit door from the inside at all times without keys, tools or special knowledge; a panic bar that locks only from the outside is allowed on exit discharge doors. Turkish workplace rules require that emergency exit doors are not locked or fastened. The narrow exceptions are places such as mental health, penal or correctional facilities with staff present at all times.
Which way should an emergency exit door open?
In the direction of escape. In Türkiye, Annex 1 of the workplace buildings regulation requires emergency exit doors to open outward and bans sliding or revolving doors as emergency exits. OSHA 1910.36(e)(2) requires the door to swing out in the direction of exit travel where the room holds more than 50 people or is a high hazard area.
How wide does an exit route have to be?
Under OSHA 1910.36(g)(2) an exit access must be at least 28 inches (71.1 cm) wide at all points, and objects that project into the route must not reduce it below the minimum. In Türkiye, the Regulation on the Fire Protection of Buildings requires escape corridors of at least 110 cm, and no exit or escape stair may be narrower than 80 cm. Wider routes are required as the number of occupants rises.
Do exit signs have to be illuminated?
Yes. OSHA 1910.37(b)(6) requires each exit sign to be lit to at least five foot-candles (54 lux) by a reliable light source, or to be self-luminous or electroluminescent, with the word Exit in letters at least six inches (15.2 cm) high. In Türkiye, emergency direction signs must stay lit for at least 60 minutes, or 120 minutes where the user load is over 200.
