Emergency Exit Inspection Checklist: Routes, Doors, Signs
Adapt this checklist to your site: edit, add, remove and reorder the checks, add your company name and logo, then save it as a PDF. Nothing is uploaded; your changes stay in this browser.
Your form
Inspection details (blank fields on the form)5 fields
The checklist · 25 checks · 5 sections
Sign-off (who signs the form)2 signers
FindRiskfindrisk.netEmergency Exit Inspection Checklist: Routes, Doors, Signs
Inspection details
Route to the exit
- 1.
The route is clear along its whole length: no stock, pallets, equipment, furniture or wasteCritical
Temporary storage counts too: a route must be clear even if the items will be moved later.
Ref.: [4] [1] [2] [5]
PassFailN/A - 2.
Nothing narrows the route below its minimum width
US: exit access at least 28 in (71.1 cm) at all points. Türkiye: escape corridors at least 110 cm; no exit or escape stair narrower than 80 cm.
Ref.: [3] [2]
PassFailN/A - 3.
Nothing hangs or projects into the route at head height
US: no projection from the ceiling lower than 6 ft 8 in (2.0 m) above the floor. Türkiye: escape corridor height at least 210 cm.
Ref.: [3] [2]
PassFailN/A - 4.
No highly flammable materials, furnishings or decorations are kept on the route
Ref.: [4]
PassFailN/A - 5.
The route does not pass through a room that can be locked
Check again after any change of layout, such as new partitions or a storeroom built across a corridor.
Ref.: [4]
PassFailN/A - 6.
The normal lighting along the route works and is bright enough to see the way
Ref.: [4] [2]
PassFailN/A - 7.
The emergency lights on the route come on when tested
Press the test button or use the test switch. This is a function check only; the duration test belongs to periodic maintenance. Türkiye: at least 60 minutes, 120 where the user load is over 200.
Ref.: [2] [1] [4] [5]
PassFailN/A
Exit signs
- 8.
The exit is marked with an exit sign that is in place and undamaged
US: the word Exit in letters at least 6 in (15.2 cm) high. Türkiye: white on green, at least 15 cm high, mounted 200 to 240 cm above the floor.
Ref.: [4] [2] [1] [5]
PassFailN/A - 9.
The exit sign is lit, and a sign with a test button stays lit when tested
Ref.: [4] [2]
PassFailN/A - 10.
Nothing hides the exit sign or the door: no stock, banners, decorations or curtains
Ref.: [4] [2]
PassFailN/A - 11.
Where the exit cannot be seen from the route, signs show the way to it
Ref.: [4] [2]
PassFailN/A - 12.
Doors on the route that could be mistaken for the exit are marked with what they are
US: marked Not an Exit or with the actual use, such as Closet.
Ref.: [4] [2]
PassFailN/A
Exit door
- 13.
The door opens from the inside without a key, tool or code; there is no padlock, chain or bolt on itCritical
Ref.: [3] [1] [2] [5]
PassFailN/A - 14.
The door opens fully and easily by hand, and the panic bar or handle worksCritical
Open it yourself. A door that sticks, drags on the floor or needs a hard push fails. Türkiye: opening force not over 110 N.
Ref.: [2] [1] [5]
PassFailN/A - 15.
The door opens in the direction of escape
Türkiye: workplace emergency exit doors open outward. US: required where the room holds more than 50 people or is a high hazard area.
Ref.: [1] [2] [3] [5]
PassFailN/A - 16.
The exit door is not a sliding or revolving door or a turnstile
Ref.: [1] [2] [5]
PassFailN/A - 17.
A door alarm or access-control device does not stop the door from being openedCritical
Mark N/A if the door has no such device.
Ref.: [3] [2]
PassFailN/A - 18.
Fire doors on the route close fully by themselves and are not wedged or tied open
Open the door fully and let go: it should close and latch. Mark N/A if the route has no fire doors.
Ref.: [3] [4] [2]
PassFailN/A
Outside the exit
- 19.
Nothing blocks the outside of the door: no vehicles, pallets, bins or stored materialsCritical
Go through the door and look. A door that opens from the inside can still be blocked from the outside.
Ref.: [1] [4] [5]
PassFailN/A - 20.
From the door, the way is open to a street, walkway or open space away from the buildingCritical
A locked yard gate or a fenced dead end fails this check.
Ref.: [3] [1] [2] [5]
PassFailN/A - 21.
Outdoor stairs and walkways on the route have guardrails on open sides and are free of snow, ice and loose surfaces
Mark N/A if the route has no outdoor part.
Ref.: [3]
PassFailN/A
Result
- 22.
Obstructions found were removed and locked doors were unlocked before leaving the exitCritical
Ref.: [4] [1] [5]
YesNoN/A - 23.
Every defect that could not be fixed on the spot has been reported to the facility manager
Ref.: [4] [2] [5]
YesNoN/A - 24.
The exit route is usable from the work area to the outsideCritical
Ref.: [4] [1] [5]
YesNo - 25.
Notes and defects found
Note: ________
Critical check: if it fails, stop and correct it before work continues.
Sign-off
Inspector
Facility manager
Legal basis and references
- [1] Türkiye: İşyeri Bina ve Eklentilerinde Alınacak Sağlık ve Güvenlik Önlemlerine İlişkin Yönetmelik (Resmî Gazete, 17.07.2013, 28710) — Annex 1, item 10 (escape routes and emergency exits: open to the outside or a safe area, unobstructed, doors open outward, no sliding or revolving doors, not locked or fastened, signs, emergency lighting) and item 35(e) (doors on escape routes open from the inside at all times).
- [2] Türkiye: Binaların Yangından Korunması Hakkında Yönetmelik (Resmî Gazete, 19.12.2007, 26735) — Article 30 (no locks or bolts that prevent escape; exits clearly visible), Article 31 (escape route defined as continuous and unobstructed), Article 33 (widths, corridor height, exits kept unobstructed), Article 47 (escape route doors), Articles 70 to 73 (emergency lighting and direction signs) and Article 84 (periodic control, testing and maintenance under the relevant standards).
- [3] United States: OSHA 29 CFR 1910.36, Design and construction requirements for exit routes — (a)(3) self-closing fire doors; (c) exit discharge; (d) unlocked exit doors and door devices; (e) door swing; (g) minimum height and width; (h) outdoor exit routes.
- [4] United States: OSHA 29 CFR 1910.37, Maintenance, safeguards, and operational features for exit routes — (a)(1) no highly flammable furnishings; (a)(3) free and unobstructed routes, no lockable rooms; (a)(4) safeguards in working order at all times; (b)(1) to (b)(7) lighting and exit signs.
- [5] United Kingdom: The Regulatory Reform (Fire Safety) Order 2005 (S.I. 2005/1541) — Applies in England and Wales. Article 14 (emergency routes and exits kept clear at all times; doors, signs and emergency lighting) and article 17 (maintenance).