Generator Inspection Checklist: Daily Pre-Use Safety Checks

Frequency
Daily
Completed by
Operator or person responsible for the generator
Approved by
Supervisor
The checklist
35 checks · 5 sections

A generator inspection checklist is the check an operator makes on a portable or mobile generator before it is put to work each day. This one covers engine-driven generators used as work equipment on a site or at a workplace: where the set stands and where its exhaust goes, fuel and refuelling, guards and hot parts, earthing, RCD or GFCI protection, sockets, extension cables, and a short running test. The operator or the person responsible for the generator completes it before the first start of the day and again when the set is moved. If a critical check fails, the generator is stopped and kept out of use until the fault has been put right.

In Türkiye, Annex III of the Work Equipment Regulation requires operators to check work equipment before each start of work, and its Table 3 lists the generator among installations that need a periodic control at least once a year unless a standard sets another period. In the United States, OSHA 29 CFR 1926.404 sets when a portable generator's frame may serve as the grounding electrode and when receptacles on construction sites need ground-fault circuit interrupters, and 1910.334 requires cord sets to be visually inspected before use on any shift. In Great Britain, HSE's guidance HSG141 says generators should not be set up or used in enclosed spaces because of carbon monoxide, that larger generators should be earthed with RCD-protected outgoing circuits, and that RCDs should be checked daily with the test button.

This daily check does not replace the periodic control of the generator and the earthing installation by an authorised person, the design of the site's electrical system by a competent electrician, or the maintenance in the manufacturer's manual. It is not written for standby sets permanently installed in a generator room, and it does not cover transfer switch or load tests. For the wider installation, see our electrical safety inspection checklist; before any repair, isolate the set as described in the lockout tagout guide.

How to use this checklist

  1. Complete the checklist each day before the generator is first started, and again whenever it is moved to a new place.
  2. Do the first three sections with the engine stopped and cool: placement and ventilation, engine and fuel, then the electrical side.
  3. Start the generator with no load connected, watch and listen for a minute, press the RCD or GFCI test button, then try the stop control.
  4. Connect the loads only after the running check. Mark checks that do not apply to your generator N/A.
  5. If a critical check fails, stop the generator, disconnect the loads, tag it "Do not use" and tell your supervisor. Never bypass an RCD, breaker or fuse to keep working.
  6. Add the daily checks from the manufacturer's manual for your model, and keep the completed forms with the equipment records.

The checklist: Generator Inspection Checklist: Daily Pre-Use Safety Checks

Inspection details

Site / area: 
Generator (make, model): 
Equipment ID or serial number: 
Type: 
Fuel: 
Rated output on the nameplate (kVA): 
Date of last periodic control: 
Date and time: 

Placement and ventilation (engine stopped)

  1. 1.

    The generator stands outdoors, not inside a building, garage, basement, crawl space or other enclosed spaceCritical

    Open doors and windows may not stop carbon monoxide from building up.

    Ref.: [7] [9] [10] [1]

    PassFailN/A
  2. 2.

    The generator is not near doors, windows, vents or air intakes through which exhaust could enter occupied spacesCritical

    Ref.: [7] [9]

    PassFailN/A
  3. 3.

    There is 3 to 4 feet (about 0.9 to 1.2 m) of clear space on all sides of the generator and above it

    This distance is from OSHA's fact sheet. Use the manufacturer's figure if it is larger.

    Ref.: [7] [9]

    PassFailN/A
  4. 4.

    The generator is dry and protected from rain; it does not stand in waterCritical

    A canopy can keep rain off an open-frame set. It must not enclose the generator or block its ventilation.

    Ref.: [7] [9] [10]

    PassFailN/A
  5. 5.

    The generator stands on firm, level ground and is secured so that it cannot move, roll or tip

    Brakes on or wheels chocked; trailer supports lowered.

    Ref.: [1]

    PassFailN/A
  6. 6.

    Fuel containers and other flammable materials are kept away from the generator and from any other source of heat or flame

    Ref.: [7] [1]

    PassFailN/A
  7. 7.

    The generator is as far from work areas and gathering places as practicable, or hearing protection is worn near it

    Ref.: [7]

    PassFailN/A

Engine and fuel (engine stopped)

  1. 8.

    The frame, housing, mountings and lifting or towing points show no cracks, loose fixings or deformation

    Ref.: [1] [9]

    PassFailN/A
  2. 9.

    The fuel tank, cap and fuel lines are tight and do not leak; there is no spilled fuel on or under the generatorCritical

    Fuel spilled on hot engine parts can ignite. Clean up any spill before starting.

    Ref.: [9] [6] [7] [1]

    PassFailN/A
  3. 10.

    Guards and covers over the fan, belt and other moving parts are in place, undamaged and firmly fixedCritical

    Ref.: [1]

    PassFailN/A
  4. 11.

    The exhaust and other hot parts are shielded or placed so that nobody can touch them by accident, and nothing combustible rests against them

    A generator stays hot for a long time after it has stopped.

    Ref.: [1] [7]

    PassFailN/A
  5. 12.

    Engine oil, and coolant on liquid-cooled sets, are at the levels given in the manufacturer's manual

    Check with the engine stopped and cool, as the manual describes.

    Ref.: [1] [9]

    PassFailN/A
  6. 13.

    The generator is refuelled only with the engine stopped and cooled downCritical

    Fill the tank before the shift so that it does not have to be topped up while hot.

    Ref.: [7] [6] [10]

    PassFailN/A
  7. 14.

    Nobody smokes and there is no open flame where the generator is refuelled or fuel is kept

    Ref.: [6] [7]

    PassFailN/A
  8. 15.

    Fuel is kept and carried only in approved containers made for fuel and marked with their contents

    Ref.: [6] [7]

    PassFailN/A
  9. 16.

    A fire extinguisher suitable for fuel and electrical fires is close to the generator and the refuelling point

    US construction rule for fuelling areas: rated at least 20-B:C and within 75 feet (about 23 m).

    Ref.: [6] [1]

    PassFailN/A

Earthing, protection and cables (engine stopped)

  1. 17.

    The generator is earthed (grounded) as the manufacturer's instructions and the site's electrical design require; any earth conductor and rod connection is tight and undamagedCritical

    OSHA lets the frame serve as the grounding electrode only when the generator supplies cord-and-plug equipment through its own receptacles and these are bonded to the frame. HSE says larger generators supplying a site should be earthed. If unsure, ask a competent electrician.

    Ref.: [2] [8] [7] [10] [1]

    PassFailN/A
  2. 18.

    The generator is not connected to the wiring of a building or cabin, unless through a transfer switch installed by a qualified electricianCritical

    A direct connection can energise the supply network and electrocute people working on it.

    Ref.: [7] [8]

    PassFailN/A
  3. 19.

    The sockets or outgoing circuits in use are protected by an RCD (GFCI) where the rules for the site require itCritical

    US construction: GFCI on 120 V single-phase 15 and 20 A receptacles, or an assured grounding program. HSE: RCD on each circuit where more than one earthed (Class I) item is supplied, and on the outgoing circuits of larger generators.

    Ref.: [2] [10] [7]

    PassFailN/A
  4. 20.

    No circuit breaker, fuse or RCD has been bypassed, bridged or disabledCritical

    A device that keeps tripping points to a fault: have a competent person find it.

    Ref.: [10] [7]

    PassFailN/A
  5. 21.

    Sockets, switches and the control panel are undamaged and dry, their covers are in place, and no live part or burn mark can be seenCritical

    Ref.: [1] [11] [10] [3]

    PassFailN/A
  6. 22.

    Extension cables, plugs and connectors have no cuts, fraying, taped joints, cracked casings or bent or missing pinsCritical

    The outer sheath should be gripped where it enters the plug: no coloured inner cores showing.

    Ref.: [4] [5] [10] [11] [7]

    PassFailN/A
  7. 23.

    Extension cables are flexible, have an earth (grounding) conductor, and are rated for the load and for outdoor or site use

    US construction: three-wire cords designed for hard or extra-hard usage. HSE: twin and earth cable is not used as an extension cable.

    Ref.: [3] [8] [7] [10]

    PassFailN/A
  8. 24.

    Cables are run where vehicles, sharp edges and doors cannot damage them, they do not lie in water, and they do not cross walkways as a trip hazard

    Ref.: [3] [4] [10]

    PassFailN/A
  9. 25.

    The total connected load does not exceed the rated output on the generator's nameplate

    Overloading leads to overheating, which can start a fire.

    Ref.: [7]

    PassFailN/A
  10. 26.

    The stop control, the emergency stop where fitted, and the main breaker can be seen, identified and reached

    Ref.: [1]

    PassFailN/A
  11. 27.

    The periodic control of the generator and of the earthing installation is in date, and the report is available

    Türkiye: at least once a year unless a standard sets another period. A mobile generator used off the premises carries its last report with it.

    Ref.: [1]

    PassFailN/A

Running check (no load connected)

  1. 28.

    The generator starts and runs without unusual noise, vibration, smoke or smellCritical

    Switch off electrical equipment that smells strange or starts to smoke, and do not use it.

    Ref.: [1] [7]

    PassFailN/A
  2. 29.

    Where fitted, the voltage, frequency, oil pressure and temperature readings are in the manufacturer's normal range and no warning is showing

    Ref.: [1]

    PassFailN/A
  3. 30.

    No fuel, oil or coolant leaks while the engine runs, and exhaust gas escapes only from the exhaust outletCritical

    Ref.: [1] [9]

    PassFailN/A
  4. 31.

    Each RCD (GFCI) trips when its test button is pressed, and resetsCritical

    HSE recommends this check daily. An RCD that does not trip is a failed critical check.

    Ref.: [10] [8]

    PassFailN/A
  5. 32.

    The stop control, and the emergency stop where fitted, stops the generatorCritical

    Ref.: [1]

    PassFailN/A

Result

  1. 33.

    Every defect found has been recorded and reported to the supervisor

    Ref.: [1] [11] [8]

    YesNoN/A
  2. 34.

    If a critical check failed, the generator is stopped, its loads are disconnected and it is tagged "Do not use" until it has been repairedCritical

    Ref.: [1] [5] [8] [10]

    YesNoN/A
  3. 35.

    Notes and defects found

    Note: ________

Critical check: if it fails, stop and correct it before work continues.

Sign-off

Operator

Name: 
Signature: 
Date: 

Supervisor

Name: 
Signature: 
Date: 

Run this checklist on your phone

FindRisk turns inspections into a few taps: AI-generated checklists you can edit and save as templates, photo markup with AI hazard analysis, Fine-Kinney risk scoring and an instant PDF report.

Download FindRisk

Legal basis and references

  1. [1] Türkiye: İş Ekipmanlarının Kullanımında Sağlık ve Güvenlik Şartları Yönetmeliği (Resmî Gazete, 25.04.2013) — Article 7 (periodic control); Annex I 2.3, 2.4, 2.6, 2.8, 2.10, 2.14, 2.17 to 2.19 (stopping, fixing, guards, hot parts, energy isolation, fire, electricity); Annex II 2.5 (combustion-engine mobile equipment only with sufficient air); Annex III 1.2, 1.3 to 1.3.2 (maintenance, operator check before each start of work, defective equipment out of use), 1.9, 2.3 and Table 3 (generator and earthing installation, 1 year).
  2. [2] United States: OSHA 29 CFR 1926.404, Wiring design and protection (construction) — (b)(1) ground-fault protection on construction sites and the exception for two-wire generators up to 5 kW; (f)(3) grounding of portable and vehicle-mounted generators. 29 CFR 1910.304(g)(3) has the same generator rule for general industry.
  3. [3] United States: OSHA 29 CFR 1926.405, Wiring methods, components, and equipment for general use (construction) — (a)(2)(ii)(I) flexible cords protected from damage; (a)(2)(ii)(J) three-wire extension cords for hard or extra-hard usage; (e)(2) and (j)(2)(ii) switches and receptacles in wet locations.
  4. [4] United States: OSHA 29 CFR 1926.416, General requirements (electrical safety-related work practices, construction) — (b)(2) walkways kept clear of cords; (e)(1) worn or frayed cords and cables not used.
  5. [5] United States: OSHA 29 CFR 1910.334, Use of equipment (electrical safety-related work practices) — (a)(2) visual inspection of cord- and plug-connected equipment and extension cords before use on any shift; defective items removed from service.
  6. [6] United States: OSHA 29 CFR 1926.152, Flammable liquids (construction) — (a)(1) approved containers; (f)(2) leakage and spillage; (g)(8) no smoking or open flames in fuelling areas; (g)(10) motors shut off during fuelling; (g)(11) fire extinguisher at fuelling areas.
  7. [7] United States: OSHA Fact Sheet, Using Portable Generators Safely (FS-3286) — Shock and backfeed, cords, GFCIs, grounding, keeping the generator dry, carbon monoxide and placement, refuelling and fuel storage, noise. Informational: it sets no new requirements.
  8. [8] United States: OSHA Fact Sheet, Grounding Requirements for Portable Generators — When the frame replaces a grounding electrode, transfer switches, cords with a grounding conductor, visual inspection before use and tagging defective equipment. Informational.
  9. [9] United States: OSHA Alert, Preventing Carbon Monoxide Poisoning While Working with Portable Generators (OSHA 4105, 2020) — Inspect for damage or loose fuel lines, keep dry, never indoors or near doors, windows and ventilation shafts, 3 to 4 feet of clear space.
  10. [10] United Kingdom: HSE, Electrical safety on construction sites, HSG141 (second edition, 2023) — Paragraphs 59, 62 to 64 (damaged equipment, cables, maintenance, RCDs never bypassed); 68, 70 and 71 (daily RCD test, user checks); 75 and 79 (IP rating, cable routes); 81 to 87 (generators: enclosed spaces, fuel, earthing, RCD protection). Guidance.
  11. [11] United Kingdom: HSE, Maintaining portable electrical equipment, HSG107 (third edition, 2013) — Paragraphs 38 and 39 (user checks on cables, plugs, sockets and extension leads; faults reported and equipment taken out of use). Used for the cables and connectors only; generators themselves are outside its scope.

Version 1 · Updated November 25, 2026 · findrisk.net/checklists/generator-inspection-checklist/

Frequently asked questions

How often should a generator be inspected?

By the operator before each day's use, plus a periodic control by an authorised person. Türkiye's Work Equipment Regulation (Annex III, 1.3) requires an operator check before each start of work, and Table 3 sets the periodic control of a generator at one year unless a standard gives another period. OSHA 1910.334(a)(2) requires extension cords and cord-connected equipment to be visually inspected before use on any shift. HSE's HSG141 says RCDs protecting 230 V portable equipment should be checked daily with the test button.

Does a portable generator need a ground rod?

Not always. Under OSHA 29 CFR 1926.404(f)(3)(i), the frame of a portable generator need not be grounded and may serve as the grounding electrode if the generator supplies only equipment mounted on it or cord-and-plug equipment through its own receptacles, and the metal parts and receptacle grounding terminals are bonded to the frame. OSHA's fact sheet adds that if these conditions do not exist, a grounding electrode such as a ground rod is required. In Great Britain, HSE's HSG141 says larger generators supplying a site should be earthed.

Can a generator be used indoors if the doors and windows are open?

No. OSHA's fact sheet on portable generators says never to use a generator indoors or in enclosed spaces such as garages, crawl spaces and basements, and notes that open windows and doors may not prevent carbon monoxide from building up. Outdoors, it should not stand near doors, windows or vents, and it needs 3 to 4 feet (about 0.9 to 1.2 m) of clear space on all sides and above. HSE's HSG141 gives the same rule for enclosed spaces.

Do the sockets on a generator need GFCI or RCD protection?

On US construction sites, OSHA 1926.404(b)(1) requires GFCIs on all 120-volt, single-phase, 15- and 20-ampere receptacles that are not part of the permanent wiring, or an assured equipment grounding conductor program instead. Receptacles on a two-wire, single-phase generator rated not more than 5 kW, with circuit conductors insulated from the frame, are excepted. HSE's HSG141 says that where more than one item of earthed (Class I) equipment is supplied from a small generator, each circuit needs RCD protection, and that the outgoing circuits of larger generators should be RCD-protected.

Can you refuel a generator while it is running?

No. OSHA's fact sheet says to shut the generator down and let it cool before refuelling, because fuel spilled on hot engine parts can ignite. For construction work, OSHA 1926.152(g) requires the motors of equipment being fuelled to be shut off and bans smoking and open flames in fuelling areas. HSE's HSG141 also calls for appropriate precautions for fuel storage and refuelling.