Fire Hose Reel Inspection Checklist: Monthly Check Form

Frequency
Monthly
Completed by
Person assigned to check fire equipment
Approved by
Facility manager
The checklist
24 checks · 4 sections

A fire hose reel inspection checklist is the routine visual check that confirms each hose reel or fire hose cabinet can be seen and reached, holds only firefighting equipment, has an undamaged hose with a shut-off nozzle connected and ready, shows no leaks, and has an in-date maintenance label. A trained member of staff completes one form per cabinet; a unit that fails a critical check is taken out of service and covered by other protection until it is repaired.

In the United States, OSHA 29 CFR 1910.158(e)(2) requires hose systems to be inspected at least annually and after each use by trained persons the employer designates, and 1910.157(e)(2) requires a monthly visual inspection where hose stations are used in place of portable extinguishers. In Türkiye, Article 94 of the Regulation on the Fire Protection of Buildings makes the periodic maintenance set out in TS EN 671-3 mandatory, and Table 3 in Annex III of the work equipment regulation sets a periodic control at least once a year unless a standard gives another interval. Turkish law sets no monthly interval; workplaces must keep firefighting equipment ready for use, visible and unobstructed at all times, and a monthly check is a common way to show that. Government guidance for England asks for a weekly look that hose reels are correctly located and in apparent working order, and formal maintenance at least annually by a competent person.

This form is the user check. It does not replace the annual maintenance and periodic control by a competent or authorised person, or any flow and pressure test. To decide where hose reels are needed, start with our fire risk assessment guide; for who does what in a fire, see the emergency action plan guide.

How to use this checklist

  1. Number every hose reel and fire hose cabinet on a floor plan and walk the same route each month, together with the fire extinguisher round.
  2. Fill one form per cabinet: its number and location, the hose type and the date on the maintenance label.
  3. Open the door, swing the reel out and look at the hose, nozzle, valve and connections. Mark each check Pass, Fail or N/A and photograph every defect.
  4. Do not run water during this check unless your site procedure says so; flow and pressure tests belong to the annual maintenance.
  5. If a critical check fails, mark the cabinet out of service, cover the area with extinguishers or a fire watch, and report it for repair the same day.
  6. Write the date and your name on the cabinet's inspection label or log, sign the form and keep it with the fire equipment records.

The checklist: Fire Hose Reel Inspection Checklist: Monthly Check Form

Inspection details

Site / building: 
Cabinet number and location: 
Hose type: 
Hose length (m): 
Date on the maintenance label: 
Date and time: 

Location, access and cabinet

  1. 1.

    The cabinet is in its designated place and easy to see from the corridor or work area

    Ref.: [1] [3] [6]

    PassFailN/A
  2. 2.

    Nothing stands in front of the cabinet or blocks its doorCritical

    Typical defects: pallets, bins, furniture, parked trolleys or stock in front of the door.

    Ref.: [3] [1] [4]

    PassFailN/A
  3. 3.

    The cabinet is marked with a permanent, visible fire hose sign

    Ref.: [3] [4] [6]

    PassFailN/A
  4. 4.

    The door opens fully and easily, without a key or toolCritical

    The cabinet must not slow down the use of the hose in a fire. A jammed, locked or painted-shut door fails.

    Ref.: [1] [4]

    PassFailN/A
  5. 5.

    The cabinet holds only firefighting equipment

    Remove cleaning materials, tools, personal items and rubbish.

    Ref.: [1] [4]

    PassFailN/A
  6. 6.

    The cabinet body, door, glass and hinges show no damage or corrosion

    Ref.: [6] [4]

    PassFailN/A

Hose, reel, nozzle and valve

  1. 7.

    The hose is connected to the water supply and ready for useCritical

    Ref.: [4] [1]

    PassFailN/A
  2. 8.

    The hose shows no cuts, cracks, kinks, flattening or abrasion along its visible lengthCritical

    Ref.: [6] [4]

    PassFailN/A
  3. 9.

    The hose is wound evenly on the reel or folded properly on its rack, and has been put back in order after its last use

    Ref.: [4]

    PassFailN/A
  4. 10.

    The reel swings out of the cabinet and turns freely

    Mark N/A for lay-flat hose on a rack or cradle.

    Ref.: [1] [4]

    PassFailN/A
  5. 11.

    A shut-off nozzle is fitted to the hose, undamaged, and its control moves freelyCritical

    Türkiye: the nozzle must provide shut-off, spray, jet, or all three.

    Ref.: [1] [4]

    PassFailN/A
  6. 12.

    The cabinet valve has its handwheel or lever, is undamaged and can be reached and operated easilyCritical

    Ref.: [4]

    PassFailN/A
  7. 13.

    There is no leak or drip at the valve, connections, reel or hose, and no water in the bottom of the cabinet

    Ref.: [6]

    PassFailN/A
  8. 14.

    The operating instructions on or beside the cabinet are in place and legible

    Ref.: [6]

    PassFailN/A

Water supply, maintenance and users

  1. 15.

    The isolating valve on the pipe feeding the cabinet is fully openCritical

    Mark N/A if there is no isolating valve you can see or reach on this route.

    Ref.: [4]

    PassFailN/A
  2. 16.

    Where a pressure gauge is fitted, it reads within the range given in the system design

    Türkiye: the design pressure at the cabinet is 400 kPa (at least 400 kPa for lay-flat hose), and pressure reducers are required where the nozzle inlet pressure would exceed 900 kPa. Mark N/A if there is no gauge.

    Ref.: [1] [4] [2]

    PassFailN/A
  3. 17.

    The hose type suits the people expected to use it

    Türkiye: where there are no trained people, a round semi-rigid hose of 25 mm, no longer than 30 m. Lay-flat hose (up to 50 mm, no longer than 20 m) only where trained firefighting staff are present.

    Ref.: [1]

    PassFailN/A
  4. 18.

    The label or record shows periodic maintenance within the last 12 months

    Türkiye: maintenance as set out in TS EN 671-3; periodic control at least yearly unless the standard sets another interval. OSHA: inspection at least annually and after each use.

    Ref.: [1] [2] [7] [4] [6]

    PassFailN/A
  5. 19.

    Staff expected to use this hose reel have been trained to use it

    OSHA: at least annual training where hose stations replace portable extinguishers.

    Ref.: [6] [5]

    YesNoN/A

Result

  1. 20.

    Every defect found has been reported to the person responsible for fire equipment

    Ref.: [1] [4]

    YesNoN/A
  2. 21.

    If a critical check failed, the cabinet is marked out of service and the area is covered by equivalent protection until it is repairedCritical

    OSHA names extinguishers and fire watches as equivalent protection.

    Ref.: [4]

    YesNoN/A
  3. 22.

    The inspection date and the inspector's name are recorded on the cabinet label or in the log

    Ref.: [6]

    YesNo
  4. 23.

    The hose reel is ready for useCritical

    Ref.: [3] [4]

    YesNo
  5. 24.

    Notes and defects found

    Note: ________

Critical check: if it fails, stop and correct it before work continues.

Sign-off

Inspector

Name: 
Signature: 
Date: 

Facility manager

Name: 
Signature: 
Date: 

Run this checklist on your phone

FindRisk turns inspections into a few taps: AI-generated checklists you can edit and save as templates, photo markup with AI hazard analysis, Fine-Kinney risk scoring and an instant PDF report.

Download FindRisk

Legal basis and references

  1. [1] Türkiye: Binaların Yangından Korunması Hakkında Yönetmelik (Resmî Gazete, 19.12.2007, 26735) — Article 94 (fire hose cabinets: where required, 30 m spacing, placement where easily seen, use only for firefighting, hose types and lengths, nozzle, design pressure, periodic maintenance under TS EN 671-3), Article 100 (owner's or manager's responsibility for periodic checks, tests and maintenance) and Article 7(10) (no blocking or misuse of fire equipment).
  2. [2] Türkiye: İş Ekipmanlarının Kullanımında Sağlık ve Güvenlik Şartları Yönetmeliği (Resmî Gazete, 25.04.2013, 28628) — Annex III, 2.3.1 (installations: periodic control yearly unless standards say otherwise), 2.3.3 (persons authorised to do it), 2.3.5 (control against the project and the fire regulation) and Table 3 (fire extinguishing systems, including fire hose cabinets).
  3. [3] Türkiye: İşyeri Bina ve Eklentilerinde Alınacak Sağlık ve Güvenlik Önlemlerine İlişkin Yönetmelik (Resmî Gazete, 17.07.2013, 28710) — Annex 1, item 12 (extinguishing equipment always ready for use, maintained, visible, easy to reach and unobstructed) and item 13 (marking with permanent, visible signs).
  4. [4] United States: OSHA 29 CFR 1910.158, Standpipe and hose systems — (c)(1) reels and cabinets: prompt use, conspicuously identified, fire equipment only; (c)(2)(i) accessible outlets; (c)(3)(i) hose connected and ready; (c)(4) shut-off nozzles; (e)(2)(i)–(ii) water supply and open valves; (e)(2)(iii) inspection at least annually and after each use; (e)(2)(iv) unserviceable systems removed from service and replaced with equivalent protection; (e)(2)(vi) trained persons.
  5. [5] United States: OSHA 29 CFR 1910.157, Portable fire extinguishers — (d)(3) hose stations used in place of Class A extinguishers, with at least annual training; (e)(2) monthly visual inspection of extinguishers or of hose used in their place.
  6. [6] United Kingdom: HM Government, Fire safety risk assessment: offices and shops (updated 12 September 2023) — Part 1, 3.4.2 and 3.4.6 (weekly check that hose reels are correctly located and in apparent working order); Part 2, 3.2 (visual checks for leaks and obvious damage, formal maintenance at least annually by a competent person, training); 3.4.5 and section 6 (signs); 7.1 (records). Guidance for England under the Regulatory Reform (Fire Safety) Order 2005.
  7. [7] European Union: EN 671-3, Fixed firefighting systems — Hose systems — Part 3: Maintenance of hose reels with semi-rigid hose and hose systems with lay-flat hose (TS EN 671-3) — The standard named by Article 94 of the Turkish fire regulation and by the guidance for England for the maintenance of hose reels (title only).

Version 1 · Updated November 25, 2026 · findrisk.net/checklists/fire-hose-reel-inspection-checklist/

Frequently asked questions

How often should fire hose reels be inspected?

OSHA 1910.158(e)(2)(iii) requires hose systems to be inspected at least annually and after each use, and 1910.157(e)(2) requires a monthly visual inspection where hose is used in place of portable extinguishers. Government guidance for England lists a weekly check that hose reels are correctly located and in apparent working order, with formal maintenance at least annually by a competent person. In Türkiye, periodic maintenance follows TS EN 671-3 and the periodic control is yearly at most; the law sets no monthly interval, so a monthly check there is good practice.

Who can inspect a fire hose reel?

Under OSHA 1910.158(e)(2)(vi) the employer designates trained persons to carry out the inspections. The guidance for England says you, or a person you have nominated, can do certain routine checks, while formal maintenance is for a competent person. In Türkiye, the yearly periodic control of fire installations is done by authorised mechanical engineers, technicians and the other professions listed in Annex III, 2.3.3 of the work equipment regulation.

What should you do if a hose reel fails the inspection?

OSHA 1910.158(e)(2)(iv) requires a hose system that is found unserviceable to be removed from service immediately and replaced with equivalent protection, such as extinguishers and fire watches. Tag the cabinet, tell the person responsible for fire equipment and have it repaired before it is counted as protection again.

What is the difference between a hose reel and a lay-flat hose cabinet?

The Turkish fire regulation separates them by who will use them. Where no trained people are present, cabinets have a round semi-rigid hose 25 mm in diameter and no longer than 30 m, to TS EN 671-1. Lay-flat hose cabinets to TS EN 671-2, with hose up to 50 mm in diameter and 20 m long, are for buildings that have trained firefighting staff.

Which buildings need fire hose cabinets in Türkiye?

Article 94 of the Regulation on the Fire Protection of Buildings requires them in high buildings, in workshops, factories, warehouses, accommodation, health, assembly and education buildings with more than 1,000 m² of enclosed floor area, in enclosed car parks over 600 m² and in boiler rooms over 350 kW. Cabinets are placed on every floor no more than 30 m apart, or up to 45 m in sprinklered buildings with fire brigade inlets on the floors.