Emergency
Emergency Lighting Inspection Checklist: Monthly Test Form
- Frequency
- Monthly
- Completed by
- Person assigned to check fire safety equipment
- Approved by
- Facility manager
- The checklist
- 27 checks · 5 sections
An emergency lighting inspection checklist is the routine test that shows the emergency luminaires and illuminated exit signs in one zone come on by themselves when the normal supply is cut, stay lit, and light the escape route, and that the yearly full-duration test and the test records are up to date. The person assigned to check fire safety equipment completes one form per floor or zone; a route whose emergency lighting fails needs temporary measures until it is repaired.
In the United States, OSHA 29 CFR 1910.37(a)(4) requires exit lighting to be in proper working order at all times, and 1910.37(b) requires exit routes to be adequately lighted and exit signs to be illuminated. OSHA sets no test interval; the routine comes from the fire code adopted where you are. The Kansas State Fire Marshal's log, for example, cites the International Fire Code and NFPA 101 section 7.9.3 and asks for a 30-second functional test every month and a 90-minute test every year. In Türkiye, Articles 70 to 73 of the Regulation on the Fire Protection of Buildings require emergency lighting that comes on automatically and runs for at least 60 minutes, or 120 minutes where the occupant load is over 200, and Article 84 requires it to be periodically checked, tested and maintained as the relevant standards set out; the regulation itself gives no interval. Government guidance for England lists a monthly function test and an annual full discharge test.
This form is the user test. It does not replace the annual check by a competent person, the periodic control of the electrical installation, or a lighting-level measurement. To decide where emergency lighting is needed, start with our fire risk assessment guide; for who does what during an evacuation, see the emergency action plan guide.
How to use this checklist
- Number every emergency luminaire and illuminated exit sign on a floor plan or list, and split the building into zones that one person can walk in a single test.
- Pick a time when the lights will not be needed straight after the test, for example early in a working day, and tell the people in the area.
- Walk the zone with the normal supply on: look for damaged or covered units, charge indicators and anything blocking the light or the signs.
- Cut the supply to the emergency lighting with the test switch or key, or press each unit's test button, and walk the route again. Mark each check Pass, Fail or N/A and write down the number of every unit that fails.
- Restore the supply, check that the units are charging again, and report every failed unit for repair the same day. Put temporary measures in place where an escape route is left without emergency lighting.
- Write the date, the zone, the result and your name in the emergency lighting log, sign the form and keep it with the fire safety records.
The checklist: Emergency Lighting Inspection Checklist: Monthly Test Form
Inspection details
Before the test: normal supply on
- 1.
Every emergency luminaire and illuminated exit sign in the zone is numbered on a plan or list
YesNoN/A - 2.
Luminaires and exit signs are in place, undamaged and not painted over or covered
Look for cracked or missing diffusers, loose fittings, water marks and units left hanging by their cable.
PassFailN/A - 3.
The charge indicator on each self-contained unit is visible and shows that the unit is charging
The meaning of the indicator colours is on the unit label or in the maker's instructions. Mark N/A where no indicator is fitted.
Ref.: [7]
PassFailN/A - 4.
The central battery or control panel shows no fault
Mark N/A for self-contained units without central controls.
Ref.: [7]
PassFailN/A - 5.
Nothing blocks the light from the luminaires or the view of the exit signs
Typical causes: high stock, new racking or partitions, banners, decorations, and other lit signs that confuse the direction of escape.
PassFailN/A - 6.PassFailN/A
- 7.
The test is being done at a time when the lights will not be needed immediately afterwards
Ref.: [7]
YesNo
Function test: normal supply cut
Use the test switch, key or each unit's test button. Do not isolate circuits you are not authorised to work on.
- 8.
The emergency lighting comes on automatically when the normal supply is cutCritical
PassFailN/A - 9.
Every emergency luminaire in the zone lights and stays lit for the whole testCritical
England: long enough to make sure each emergency lamp illuminates. Kansas fire marshal's log (IFC, NFPA 101 section 7.9.3): 30 seconds every month. Write the number of each failed unit in the notes.
PassFailN/A - 10.PassFailN/A
- 11.
The lamps give a steady light, with no unit clearly dimmer than the others or flickering
Ref.: [7]
PassFailN/A - 12.
With the normal lighting off, exit doors, corridors and their intersections, stairs and changes in floor level are lit well enough to walk the route
Türkiye: at least 1 lux on the centre line of the escape route. This form does not ask you to measure it; report dark stretches for assessment.
PassFailN/A - 13.
Fire alarm call points and firefighting equipment on the route can be seen in the emergency lighting
Ref.: [7]
PassFailN/A - 14.
The area outside each final exit and any external escape route is lit
Mark N/A if the zone has no final exit.
Ref.: [7]
PassFailN/A - 15.
Where a generator feeds the emergency lighting, it has been test-run this month
The England guide's example checklist: emergency generators tested monthly, normally run for one hour. Mark N/A if there is no generator.
Ref.: [7]
YesNoN/A - 16.
Safety torches kept for escape are in their places and work
Mark N/A if torches are not part of your arrangements.
Ref.: [7]
PassFailN/A
After the test
Duration test, yearly check and earlier defects
- 19.
The log shows a full-duration test of this zone within the last 12 months, and every unit lasted its rated time
Türkiye: at least 60 minutes, 120 minutes where the occupant load is over 200. England: annual full discharge test. Kansas fire marshal's log: 90 minutes every year.
YesNoN/A - 20.
After a full-duration test, the area is not used in darkness until the batteries have recharged, unless other arrangements are in place
The England guide notes that batteries typically take 24 hours to recharge. Mark N/A for a monthly function test.
Ref.: [7]
YesNoN/A - 21.
The records show that a competent person has tested and maintained the system within the last 12 months
Türkiye: periodic control, testing and maintenance as the relevant standards set out; the electrical installation is periodically controlled at least yearly by authorised persons unless a standard gives another interval.
YesNoN/A - 22.YesNoN/A
Result
- 23.
Every failed unit has been reported, with its number, to the person responsible for the building's fire safety systems
YesNoN/A - 24.
If a critical check failed, temporary measures cover the affected escape route until the lighting is repairedCritical
For example torches for trained staff, or not using the area in darkness.
YesNoN/A - 25.
The date, zone, units tested, result and tester's name are entered in the emergency lighting log
YesNo - 26.YesNo
- 27.
Notes and numbers of failed units
Note: ________
Critical check: if it fails, stop and correct it before work continues.
Sign-off
Tester
Facility manager
Run this checklist on your phone
FindRisk turns inspections into a few taps: AI-generated checklists you can edit and save as templates, photo markup with AI hazard analysis, Fine-Kinney risk scoring and an instant PDF report.
Download FindRiskLegal basis and references
- [1] Türkiye: Binaların Yangından Korunması Hakkında Yönetmelik (Resmî Gazete, 19.12.2007, 26735) — Article 70 (emergency lighting switches on automatically), 71 (all escape routes and stairs lit), 72 (automatic operation, at least 60 minutes or 120 minutes where the occupant load is over 200, at least 1 lux on the route centre line), 73 (direction signs: lit, duration, colours, size, height, visibility), 84 (periodic control, testing and maintenance of emergency lighting and direction systems as the relevant standards set out) and 67 (owner's or manager's responsibility).
- [2] Türkiye: İşyeri Bina ve Eklentilerinde Alınacak Sağlık ve Güvenlik Önlemlerine İlişkin Yönetmelik (Resmî Gazete, 17.07.2013, 28710) — Annex 1, item 10(e) and (f) (marking of escape routes and exits; emergency lighting on a separate energy source where they need lighting) and item 24 (emergency lighting where a lighting failure could create a risk).
- [3] Türkiye: İş Ekipmanlarının Kullanımında Sağlık ve Güvenlik Şartları Yönetmeliği (Resmî Gazete, 25.04.2013, 28628) — Annex III, 2.3.1 (installations: periodic control yearly unless standards say otherwise), 2.3.2 (persons authorised to control electrical installations) and Table 3 (electrical installation: one year unless a standard gives an interval).
- [4] United States: OSHA 29 CFR 1910.37, Maintenance, safeguards, and operational features for exit routes — (a)(4) safeguards such as exit lighting in proper working order at all times; (b)(1) exit routes adequately lighted; (b)(2)–(b)(4) exits marked, signs not obscured, line of sight to exit signs; (b)(6) exit signs illuminated to at least five foot-candles (54 lux). The section sets no test interval.
- [5] United States: OSHA 29 CFR 1910.35, Compliance with alternate exit-route codes — Compliance with the exit-route provisions of NFPA 101 (2009 edition) or the International Fire Code (2009 edition) is deemed compliance with 1910.34, 1910.36 and 1910.37. Used in the introduction and FAQs.
- [6] United States: Kansas Office of the State Fire Marshal, Fire Fact 050: Emergency Lights/Signs Log — State example of the fire-code routine, citing the International Fire Code and NFPA 101 section 7.9.3: 30-second functional test every month, 90-minute test every year, a dated and initialled entry for each unit, comments on failure and replacement, documentation kept.
- [7] United Kingdom: HM Government, Fire safety risk assessment: offices and shops (updated 12 September 2023) — Part 1, 3.4.4 (when emergency escape lighting is needed, torches) and 3.4.6 (daily, monthly and annual checks); Part 2, Section 5 (what the lighting should cover, function test, annual full discharge test, recharge time, records; names BS 5266-1 and BS 5266-8 for further guidance); 7.1 (records and plans); Appendix A1 (example checklist). Guidance for England under the Regulatory Reform (Fire Safety) Order 2005.
- [8] United Kingdom: The Regulatory Reform (Fire Safety) Order 2005 (S.I. 2005/1541) — Article 14(2)(h) (emergency lighting of adequate intensity on routes and exits that need illumination, in case the normal lighting fails) and Article 17(1) (suitable system of maintenance; efficient working order and good repair).
Version 1 · Updated November 26, 2026 · findrisk.net/checklists/emergency-lighting-inspection-checklist/
Fill in this checklist on your phone. Scan to download FindRisk: run the checklist, add photos, score risks and share a PDF report in minutes.
Version 1 · Updated November 26, 2026 · findrisk.net/checklists/emergency-lighting-inspection-checklist/
Frequently asked questions
How often should emergency lighting be tested?
It depends on the code that applies to your building. The Kansas State Fire Marshal's log, which cites the International Fire Code and NFPA 101 section 7.9.3, asks for a 30-second functional test every month and a 90-minute test once a year. Government guidance for England lists a daily visual check of any central controls, a monthly function test and an annual full discharge test. The Turkish fire regulation requires periodic control, testing and maintenance as the relevant standards set out, without giving an interval of its own.
Does OSHA require emergency lights to be tested monthly?
OSHA's exit route standard does not set a test interval. 29 CFR 1910.37(a)(4) requires safeguards such as exit lighting to be in proper working order at all times, and 1910.37(b) requires exit routes to be adequately lighted and exit signs to be illuminated to at least five foot-candles (54 lux). Under 1910.35, an employer who complies with the exit-route provisions of NFPA 101 or the International Fire Code (2009 editions) is deemed to comply with the OSHA exit route rules. Monthly and annual tests come from those fire codes as adopted by your state or city.
What is the difference between a function test and a duration test?
A function test is short: you cut the normal supply for long enough to see that every lamp and sign lights. The guidance for England describes it as operating the test facility for a period sufficient to ensure that each emergency lamp illuminates. A duration test runs the lights on their batteries for the full rated time, which shows whether the batteries still hold their charge. The same guidance notes that batteries typically take 24 hours to recharge afterwards.
How long must emergency lighting stay on?
In Türkiye, Article 72 of the Regulation on the Fire Protection of Buildings requires at least 60 minutes, and at least 120 minutes where the occupant load is over 200. The guidance for England says systems are designed to operate for between one and three hours. The Kansas State Fire Marshal's log sets the annual test at 90 minutes. Check the rated duration on the unit label or in the system design, and test against that.
Who can carry out the monthly emergency lighting test?
The guidance for England says you should be able to carry out most of the routine tests yourself, and that the emergency lighting should be tested and maintained by a competent person every year. In Türkiye, the building owner, manager or the official they have delegated is responsible for periodic control, testing and maintenance, and the yearly periodic control of the electrical installation is done by authorised electrical engineers or technicians.
