Inspection details
Location and access
Walk to the station from the place where a splash could happen.
- 1.
The station can be reached from the hazard in about 10 seconds
ANSI Z358.1, as summarised by CCOHS: an average person walks 16 to 17 m (55 ft) in 10 seconds.
Ref.: [3] [1]
PassFailN/A - 2.
It is on the same floor as the hazard, with no stairs or doors to pass on the way
Ref.: [3]
PassFailN/A - 3.
The route to the station is clear of stored materials, equipment and other obstacles
Ref.: [3] [5] [1] [8]
PassFailN/A - 4.
The station is marked with a highly visible sign
Ref.: [3] [4]
PassFailN/A - 5.
The area around the station is well lit
Ref.: [3] [4]
PassFailN/A - 6.
Nothing is stored in, on or directly around the unit
ANSI Z358.1, as summarised by CCOHS: nozzles at least 15 cm (6 in) from the wall or nearest obstruction and 83.8 to 134.6 cm (33 to 53 in) above the floor.
Ref.: [3] [4] [5]
PassFailN/A
Condition of the unit
Visual checks before the water is turned on.
- 7.
Both nozzles have their dust covers, and the covers are clean and undamaged
Ref.: [3] [4]
PassFailN/A - 8.
The bowl and nozzles are clean, with no dirt, scale or debris
Ref.: [5] [3]
PassFailN/A - 9.
No water leaks from the valve, pipework or fittings
Ref.: [4] [5]
PassFailN/A - 10.
An outdoor or unheated station is protected from freezing
Mark N/A for stations in heated indoor areas.
Ref.: [3]
PassFailN/A - 11.
Self-contained unit: the tank is full and the flushing fluid is within its dateCritical
Change the fluid and clean the tank as the manufacturer's instructions say, using only solutions meant for flushing eyes. Mark N/A for plumbed units.
Ref.: [2] [3]
PassFailN/A - 12.
Eyewash bottles kept at the station are sealed and within their expiry date
Bottles supplement a station; they do not replace it. Mark N/A if there are none.
Ref.: [6] [3]
PassFailN/A
Activation test
Plumbed units: open the valve and let the water run. Self-contained units: follow the manufacturer's instructions and mark N/A where a check would empty the tank.
- 13.
The valve opens with one movement and water arrives within about a secondCritical
Ref.: [2] [3]
PassFailN/A - 14.
The water keeps running after the hand is taken off the valveCritical
Ref.: [2] [3] [5]
PassFailN/A - 15.
The dust covers come off by the water flow alone
Covers that stay on can be a sign of low flow.
Ref.: [3] [4]
PassFailN/A - 16.
Water flows from both nozzles at the same time, in even streamsCritical
Ref.: [3] [4]
PassFailN/A - 17.
The streams rise high enough to reach both eyes and do not trickleCritical
Ref.: [4] [5]
PassFailN/A - 18.
The unit was run long enough to clear the standing water from the supply pipe
Follow the manufacturer's instructions for how long. Stagnant water can carry organisms that infect an injured eye.
Ref.: [2] [3] [5]
PassFailN/A - 19.
After flushing, the water runs clear, with no colour, particles or smellCritical
Ref.: [4] [2]
PassFailN/A - 20.
The water feels lukewarm, neither hot nor ice-cold
ANSI Z358.1, as summarised by CCOHS, defines tepid as 16 to 38 °C (60 to 100 °F). Temperature is measured at the annual inspection.
Ref.: [3] [2]
PassFailN/A - 21.
The water drains away and any spilled water has been wiped up
Ref.: [3] [4]
PassFailN/A
Records and instruction
- 22.
The tag or log shows a full inspection within the last 12 months
Ref.: [3]
PassFailN/A - 23.
Today's date and the inspector's initials are written on the station's tag or log
Ref.: [3] [4]
YesNo - 24.
People working in the area have been shown where the station is and how to use it
Ref.: [3] [7]
YesNoN/A
Result
- 25.
Every defect found has been reported to the supervisor and a repair requested
Ref.: [5]
YesNoN/A - 26.
If a critical check failed, the station is tagged out of service and work with hazardous materials in the area does not go on without another means of flushing the eyesCritical
Ref.: [5] [1] [7]
YesNoN/A - 27.
The station is ready for use, with the nozzle covers back in placeCritical
Ref.: [1] [8] [5]
YesNo - 28.
Notes and defects found
Note: ________
Critical check: if it fails, stop and correct it before work continues.
Sign-off
Inspector
Area supervisor
Legal basis and references
- [1] United States: OSHA 29 CFR 1910.151, Medical services and first aid — Paragraph (c): suitable facilities for quick drenching or flushing of the eyes and body within the work area for immediate emergency use. Sets no test interval. 29 CFR 1926.50(g) has the same wording for construction.
- [2] United States: OSHA InfoSheet, Health Effects from Contaminated Water in Eyewash Stations (OSHA 3818, 2015) — ANSI performance figures (tepid fluid, 1.5 L/min for 15 minutes, single movement, hands-free); organisms in stagnant water; manufacturer's instructions for how often and how long to activate plumbed units and for maintaining self-contained units. Advisory, not a regulation.
- [3] International: Canadian Centre for Occupational Health and Safety (CCOHS), Emergency Showers and Eyewash Stations (fact sheet, revised 2024-03-15) — Public summary of ANSI/ISEA Z358.1-2014 (R2020): 10-second reach, same level, clear path, sign and lighting, valve operation, flow rates, nozzle height and clearance, covers, tepid range, weekly activation, annual inspection, self-contained units, records, instruction, drainage and freeze protection. The standard itself was not consulted.
- [4] United States: University of Arkansas, Office of Environmental Health and Safety, Emergency Eye/Face Wash Station Weekly Inspection Checklist (revised June 2023) — Institutional weekly practice: sign and lighting, clearance, clear water, even flow from all nozzles, hands-free flow that does not trickle, caps that open on activation, leaks, dated and initialled log.
- [5] International: University of Waterloo Safety Office, Eye/Face Wash and Drench Hose Weekly Inspection (v.1.1, May 2023) — Institutional weekly practice: clear pathway, no leaks, clean unit, flushing stagnant water from the dead leg, hands-free flow, flow pattern; when a problem is found, report it, tag out the station and use no hazardous materials until it is repaired.
- [6] United Kingdom: HSE, Frequently asked questions on first aid — Eye irrigation where mains tap water is not readily available: at least one litre of sterile water or sterile normal saline (0.9%) in sealed, disposable containers, not reused once opened and not used after the expiry date.
- [7] Türkiye: Kimyasal Maddelerle Çalışmalarda Sağlık ve Güvenlik Önlemleri Hakkında Yönetmelik (Resmî Gazete, 12.08.2013, 28733) — Article 8 (emergencies): measures to reduce the effects of chemical emergencies are taken at once and emergency response procedures are kept ready. The regulation does not name eyewash stations.
- [8] Türkiye: İşyeri Bina ve Eklentilerinde Alınacak Sağlık ve Güvenlik Önlemlerine İlişkin Yönetmelik (Resmî Gazete, 17.07.2013, 28710) — Annex 1, item 60: first-aid equipment is kept in easily accessible places wherever working conditions require it. The regulation does not name eyewash stations.
Fill in this checklist on your phone. Scan to download FindRisk: run the checklist, add photos, score risks and share a PDF report in minutes.
This form was customized by its user from a FindRisk template. It is a guide and does not replace a risk assessment or the periodic inspection by a competent person.
Based on the template at: findrisk.net/checklists/eyewash-station-inspection-checklist/ · Version 1