{"$schema":"https://findrisk.net/checklists/schema.json","schemaVersion":1,"id":"generator-inspection-checklist","version":1,"date":"2026-11-25T21:27:21+03:00","category":"equipment","industries":["general","construction","manufacturing","energy-utilities"],"frequency":"daily","page":{"en":{"slug":"generator-inspection-checklist","title":"Generator Inspection Checklist: Daily Pre-Use Safety Checks","description":"Free generator inspection checklist: daily checks for placement and exhaust, fuel, earthing, RCD or GFCI, cables and a running test, with the source of each.","intro":"A **generator inspection checklist** is the check an operator makes on a portable or mobile generator before it is put to work each day. This one covers engine-driven generators used as work equipment on a site or at a workplace: where the set stands and where its exhaust goes, fuel and refuelling, guards and hot parts, earthing, RCD or GFCI protection, sockets, extension cables, and a short running test. The operator or the person responsible for the generator completes it before the first start of the day and again when the set is moved. If a critical check fails, the generator is stopped and kept out of use until the fault has been put right.\n\nIn Türkiye, Annex III of the Work Equipment Regulation requires operators to check work equipment before each start of work, and its Table 3 lists the generator among installations that need a periodic control at least once a year unless a standard sets another period. In the United States, OSHA 29 CFR 1926.404 sets when a portable generator's frame may serve as the grounding electrode and when receptacles on construction sites need ground-fault circuit interrupters, and 1910.334 requires cord sets to be visually inspected before use on any shift. In Great Britain, HSE's guidance HSG141 says generators should not be set up or used in enclosed spaces because of carbon monoxide, that larger generators should be earthed with RCD-protected outgoing circuits, and that RCDs should be checked daily with the test button.\n\nThis daily check does not replace the periodic control of the generator and the earthing installation by an authorised person, the design of the site's electrical system by a competent electrician, or the maintenance in the manufacturer's manual. It is not written for standby sets permanently installed in a generator room, and it does not cover transfer switch or load tests. For the wider installation, see our [electrical safety inspection checklist](/blog/electrical-safety-inspection-checklist); before any repair, isolate the set as described in the [lockout tagout guide](/blog/lockout-tagout-loto-guide).","howToUse":["Complete the checklist each day before the generator is first started, and again whenever it is moved to a new place.","Do the first three sections with the engine stopped and cool: placement and ventilation, engine and fuel, then the electrical side.","Start the generator with no load connected, watch and listen for a minute, press the RCD or GFCI test button, then try the stop control.","Connect the loads only after the running check. Mark checks that do not apply to your generator N/A.","If a critical check fails, stop the generator, disconnect the loads, tag it \"Do not use\" and tell your supervisor. Never bypass an RCD, breaker or fuse to keep working.","Add the daily checks from the manufacturer's manual for your model, and keep the completed forms with the equipment records."],"faqs":[{"question":"How often should a generator be inspected?","answer":"By the operator before each day's use, plus a periodic control by an authorised person. Türkiye's Work Equipment Regulation (Annex III, 1.3) requires an operator check before each start of work, and Table 3 sets the periodic control of a generator at one year unless a standard gives another period. OSHA 1910.334(a)(2) requires extension cords and cord-connected equipment to be visually inspected before use on any shift. HSE's HSG141 says RCDs protecting 230 V portable equipment should be checked daily with the test button."},{"question":"Does a portable generator need a ground rod?","answer":"Not always. Under OSHA 29 CFR 1926.404(f)(3)(i), the frame of a portable generator need not be grounded and may serve as the grounding electrode if the generator supplies only equipment mounted on it or cord-and-plug equipment through its own receptacles, and the metal parts and receptacle grounding terminals are bonded to the frame. OSHA's fact sheet adds that if these conditions do not exist, a grounding electrode such as a ground rod is required. In Great Britain, HSE's HSG141 says larger generators supplying a site should be earthed."},{"question":"Can a generator be used indoors if the doors and windows are open?","answer":"No. OSHA's fact sheet on portable generators says never to use a generator indoors or in enclosed spaces such as garages, crawl spaces and basements, and notes that open windows and doors may not prevent carbon monoxide from building up. Outdoors, it should not stand near doors, windows or vents, and it needs 3 to 4 feet (about 0.9 to 1.2 m) of clear space on all sides and above. HSE's HSG141 gives the same rule for enclosed spaces."},{"question":"Do the sockets on a generator need GFCI or RCD protection?","answer":"On US construction sites, OSHA 1926.404(b)(1) requires GFCIs on all 120-volt, single-phase, 15- and 20-ampere receptacles that are not part of the permanent wiring, or an assured equipment grounding conductor program instead. Receptacles on a two-wire, single-phase generator rated not more than 5 kW, with circuit conductors insulated from the frame, are excepted. HSE's HSG141 says that where more than one item of earthed (Class I) equipment is supplied from a small generator, each circuit needs RCD protection, and that the outgoing circuits of larger generators should be RCD-protected."},{"question":"Can you refuel a generator while it is running?","answer":"No. OSHA's fact sheet says to shut the generator down and let it cool before refuelling, because fuel spilled on hot engine parts can ignite. For construction work, OSHA 1926.152(g) requires the motors of equipment being fuelled to be shut off and bans smoking and open flames in fuelling areas. HSE's HSG141 also calls for appropriate precautions for fuel storage and refuelling."}],"tags":["generator","portable generator","carbon monoxide","earthing and grounding","RCD and GFCI","daily inspection"]},"tr":{"slug":"jenerator-kontrol-listesi","title":"Jeneratör Kontrol Listesi: Günlük Kontrol Formu","description":"Ücretsiz jeneratör kontrol listesi: yer ve egzoz, yakıt, topraklama, kaçak akım rölesi, priz ve kablolar ile çalışma denemesi için günlük kontrol formu.","intro":"**Jeneratör kontrol listesi**, operatörün seyyar bir jeneratörü her gün işe almadan önce yaptığı kontroldür. Bu form, şantiyede veya işyerinde iş ekipmanı olarak kullanılan içten yanmalı motorlu jeneratörleri kapsar: jeneratörün durduğu yer ve egzozun yönü, yakıt ve yakıt ikmali, muhafazalar ve sıcak yüzeyler, topraklama, kaçak akım koruması, prizler, uzatma kabloları ve kısa bir çalışma denemesi. Formu operatör ya da jeneratörden sorumlu kişi günün ilk çalıştırmasından önce doldurur; jeneratör başka bir yere taşındığında yeniden doldurur. Kritik bir maddede uygunsuzluk varsa jeneratör durdurulur ve arıza giderilene kadar kullanım dışı bırakılır.\n\nİş Ekipmanlarının Kullanımında Sağlık ve Güvenlik Şartları Yönetmeliği'nin Ek-III'ü (madde 1.3), iş ekipmanlarının her çalışmaya başlamadan önce operatörleri tarafından kontrol edilmesini, gözle muayene ve fonksiyon denemesinin kayıt altına alınmasını ister. Aynı ekin Tablo-3'ü jeneratörü periyodik kontrole tabi tesisatlar arasında sayar: standartlarda süre belirtilmemişse periyodik kontrol yılda bir yapılır. Ek-II madde 2.5 ise içten yanmalı motorlu seyyar iş ekipmanının ancak çalışanlar için risk yaratmayacak yeterli hava sağlanması şartıyla kullanılmasına izin verir. Topraklama, kaçak akım koruması, kablo ve yakıt ikmaliyle ilgili maddelerin ayrıntısı, Yönetmeliğin genel hükümlerinin yanında ABD'deki OSHA kurallarına (29 CFR 1926.404, 1926.152) ve İngiltere'deki HSE'nin HSG141 rehberine dayanır; her maddenin kaynağı formun sonunda yazılıdır.\n\nBu günlük kontrol, jeneratörün ve topraklama tesisatının yetkili kişilerce yapılan periyodik kontrolünün, elektrik tesisatının projesinin ya da imalatçının kullanım kılavuzundaki bakımın yerine geçmez. Jeneratör odasına sabit kurulmuş yedek güç jeneratörleri için hazırlanmamıştır; transfer şalteri ve yük testlerini kapsamaz. Tesisatın geneli için [elektrik güvenliği kontrol listemize](/blog/electrical-safety-inspection-checklist) bakın; onarımdan önce jeneratörün enerjisini kesmek için [kilitleme ve etiketleme (LOTO) rehberimizi](/blog/lockout-tagout-loto-guide) izleyin.","howToUse":["Listeyi her gün jeneratör ilk kez çalıştırılmadan önce, jeneratör yeni bir yere taşındığında ise yeniden doldurun.","İlk üç bölümü motor dururken ve soğukken yapın: yer ve havalandırma, motor ve yakıt, sonra elektrik tarafı.","Jeneratörü yük bağlamadan çalıştırın, bir dakika izleyip dinleyin, kaçak akım rölesinin test düğmesine basın, sonra durdurma kumandasını deneyin.","Yükleri çalışma kontrolünden sonra bağlayın. Jeneratörünüzde olmayan maddeleri Kapsam dışı işaretleyin.","Kritik bir madde uygun değilse jeneratörü durdurun, yükleri ayırın, \"Kullanmayın\" etiketi asın ve amirinize haber verin. Çalışmaya devam etmek için kaçak akım rölesini, şalteri veya sigortayı asla köprülemeyin.","Kullanım kılavuzunda modele özel günlük kontroller varsa listeye ekleyin; doldurulan formları ekipman kayıtlarıyla birlikte saklayın."],"faqs":[{"question":"Jeneratör ne sıklıkla kontrol edilmeli?","answer":"Operatör tarafından her çalışmaya başlamadan önce, yetkili kişi tarafından da periyodik olarak. İş Ekipmanlarının Kullanımında Sağlık ve Güvenlik Şartları Yönetmeliği Ek-III madde 1.3, iş ekipmanlarının her çalışmaya başlamadan önce operatörlerince kontrol edilmesini; madde 1.3.1 günlük muayenede çatlak, gevşemiş bağlantı, deformasyon, aşınma ve korozyon bakımından gözle muayene yapılmasını ve fonksiyonların denenmesini ister. Periyodik kontrol ayrıdır ve bu formun yerine geçmez."},{"question":"Jeneratörün periyodik kontrolü kaç yılda bir yapılır, kim yapar?","answer":"Yönetmeliğin Ek-III Tablo-3'üne göre jeneratörün periyodik kontrol süresi, standartlarda süre belirtilmemişse 1 yıldır ve kontrol TS ISO 8528 serisi standartlardaki kriterlere göre yapılır. Aynı tabloda elektrik tesisatı ve topraklama tesisatı için de süre, standartlarda belirtilmemişse 1 yıldır. Madde 2.3.2'ye göre bu kontrolleri yetkili elektrik mühendisleri, elektrik-elektronik mühendisleri, elektrik eğitimi bölümü mezunu teknik öğretmenler ile elektrik teknikerleri ve yüksek teknikerleri yapar. Seyyar jeneratör işletme dışında kullanılıyorsa son periyodik kontrol raporu ekipmanla birlikte bulundurulur (madde 7)."},{"question":"Seyyar jeneratöre topraklama çubuğu gerekir mi?","answer":"Jeneratörün tipine ve neyi beslediğine göre değişir; kararı kullanım kılavuzuna ve tesisatın projesine göre yetkili bir elektrikçi verir. ABD'deki OSHA kuralı (29 CFR 1926.404(f)(3)), jeneratör yalnızca kendi üzerindeki prizlerden fişli ekipmanı besliyorsa ve metal kısımlar ile prizlerin toprak uçları şasiye bağlıysa şasinin topraklama elektrodu sayılmasına izin verir; bu şartlar yoksa topraklama çubuğu gerekir. İngiltere'deki HSE'nin HSG141 rehberi, şantiyeyi besleyen büyük jeneratörlerin topraklanmasını ve çıkış devrelerinin kaçak akım korumalı olmasını ister. Türkiye'de topraklama tesisatının periyodik kontrol kriteri olarak Yönetmeliğin Tablo-3'ü Elektrik Tesislerinde Topraklamalar Yönetmeliği'ni gösterir."},{"question":"Jeneratör kapalı alanda çalıştırılır mı?","answer":"Hayır. Yönetmeliğin Ek-II madde 2.5 hükmü, içten yanmalı motorlu seyyar iş ekipmanının ancak çalışanlar için risk yaratmayacak yeterli hava sağlanırsa kullanılmasına izin verir. OSHA'nın seyyar jeneratör bilgi notu, jeneratörün bina içinde, garaj ve bodrum gibi kapalı yerlerde asla çalıştırılmamasını, kapı ve pencereleri açmanın karbonmonoksit birikmesini önlemeyebileceğini söyler. Açık havada da kapı, pencere ve havalandırma ağızlarının yakınına konmaz; her yanında ve üstünde 3 - 4 fit (yaklaşık 0,9 - 1,2 m) boşluk bırakılır."},{"question":"Jeneratör çalışırken yakıt doldurulur mu?","answer":"Hayır. OSHA'nın bilgi notu, yakıt doldurmadan önce jeneratörün durdurulmasını ve soğumaya bırakılmasını ister; sıcak motor parçalarına dökülen yakıt tutuşabilir. ABD'nin inşaat kuralı OSHA 1926.152(g), yakıt ikmali sırasında motorun kapatılmasını ve ikmal yapılan yerde sigara içilmemesini, açık alev bulunmamasını şart koşar. HSE'nin HSG141 rehberi de yakıtın depolanması ve ikmali için uygun önlemlerin alınmasını söyler."}],"tags":["jeneratör","seyyar jeneratör","karbonmonoksit","topraklama","kaçak akım rölesi","günlük kontrol","periyodik kontrol"]}},"roles":{"completedBy":{"en":"Operator or person responsible for the generator","tr":"Operatör veya jeneratör sorumlusu"},"approvedBy":{"en":"Supervisor","tr":"Amir"}},"header":[{"id":"site","label":{"en":"Site / area","tr":"İşyeri / alan"},"type":"text"},{"id":"equipment","label":{"en":"Generator (make, model)","tr":"Jeneratör (marka, model)"},"type":"text"},{"id":"equipment-id","label":{"en":"Equipment ID or serial number","tr":"Ekipman no veya seri no"},"type":"text"},{"id":"generator-type","label":{"en":"Type","tr":"Tip"},"type":"select","options":[{"id":"portable","label":{"en":"Portable (carried or wheeled)","tr":"Portatif (elle taşınan veya tekerlekli)"}},{"id":"mobile","label":{"en":"Mobile (trailer or skid mounted)","tr":"Seyyar (römorklu veya kızaklı)"}}]},{"id":"fuel","label":{"en":"Fuel","tr":"Yakıt"},"type":"select","options":[{"id":"petrol","label":{"en":"Petrol (gasoline)","tr":"Benzin"}},{"id":"diesel","label":{"en":"Diesel","tr":"Motorin (dizel)"}},{"id":"other","label":{"en":"Other","tr":"Diğer"}}]},{"id":"rated-output","label":{"en":"Rated output on the nameplate","tr":"Etiketteki anma gücü"},"type":"number","unit":"kVA","required":false},{"id":"last-periodic-control","label":{"en":"Date of last periodic control","tr":"Son periyodik kontrol tarihi"},"type":"date","required":false},{"id":"inspected-at","label":{"en":"Date and time","tr":"Tarih ve saat"},"type":"datetime"}],"sections":[{"id":"location","title":{"en":"Placement and ventilation (engine stopped)","tr":"Yer ve havalandırma (motor dururken)"},"items":[{"id":"outdoors","text":{"en":"The generator stands outdoors, not inside a building, garage, basement, crawl space or other enclosed space","tr":"Jeneratör açık havada duruyor; bina içinde, garajda, bodrumda veya başka bir kapalı alanda değil"},"guidance":{"en":"Open doors and windows may not stop carbon monoxide from building up.","tr":"Kapı ve pencerelerin açık olması karbonmonoksit birikmesini önlemeyebilir."},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["osha-fs-generators","osha-co-alert","hse-hsg141","tr-is-ekipmanlari"]},{"id":"away-from-openings","text":{"en":"The generator is not near doors, windows, vents or air intakes through which exhaust could enter occupied spaces","tr":"Jeneratör, egzoz gazının içeride insan bulunan yerlere girebileceği kapı, pencere, menfez veya hava emişlerinin yakınında değil"},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["osha-fs-generators","osha-co-alert"]},{"id":"clearance","text":{"en":"There is 3 to 4 feet (about 0.9 to 1.2 m) of clear space on all sides of the generator and above it","tr":"Jeneratörün her yanında ve üstünde 3 - 4 fit (yaklaşık 0,9 - 1,2 m) boşluk var"},"guidance":{"en":"This distance is from OSHA's fact sheet. Use the manufacturer's figure if it is larger.","tr":"Bu mesafe OSHA'nın bilgi notundan alınmıştır. Kullanım kılavuzundaki değer daha büyükse onu uygulayın."},"response":"pass-fail-na","refs":["osha-fs-generators","osha-co-alert"]},{"id":"dry","text":{"en":"The generator is dry and protected from rain; it does not stand in water","tr":"Jeneratör kuru ve yağmurdan korunuyor; su birikintisi içinde durmuyor"},"guidance":{"en":"A canopy can keep rain off an open-frame set. It must not enclose the generator or block its ventilation.","tr":"Açık şasili jeneratör bir sundurmayla yağmurdan korunabilir. Sundurma jeneratörü kapatmamalı, havalandırmasını kesmemeli."},"response":"pass-fail-na","critical":true,"refs":["osha-fs-generators","osha-co-alert","hse-hsg141"]},{"id":"stable","text":{"en":"The generator stands on firm, level ground and is secured so that it cannot move, roll or tip","tr":"Jeneratör sağlam ve düz bir zeminde duruyor; kaymayacak, yürümeyecek veya devrilmeyecek şekilde sabitlenmiş"},"guidance":{"en":"Brakes on or wheels chocked; trailer supports lowered.","tr":"Frenler çekili veya tekerlekler takozlu; römork ayakları indirilmiş."},"response":"pass-fail-na","refs":["tr-is-ekipmanlari"]},{"id":"fuel-kept-away","text":{"en":"Fuel containers and other flammable materials are kept away from the generator and from any other source of heat or flame","tr":"Yakıt bidonları ve diğer yanıcı malzemeler jeneratörden ve başka ısı veya alev kaynaklarından uzakta tutuluyor"},"response":"pass-fail-na","photo":"required-on-fail","refs":["osha-fs-generators","tr-is-ekipmanlari"]},{"id":"noise-distance","text":{"en":"The generator is as far from work areas and gathering places as practicable, or hearing protection is worn near it","tr":"Jeneratör çalışma ve toplanma alanlarından mümkün olduğunca uzakta; değilse yakınında kulak koruyucu kullanılıyor"},"response":"pass-fail-na","refs":["osha-fs-generators"]}]},{"id":"engine-fuel","title":{"en":"Engine and fuel (engine stopped)","tr":"Motor ve yakıt (motor dururken)"},"items":[{"id":"unit-condition","text":{"en":"The frame, housing, mountings and lifting or towing points show no cracks, loose fixings or deformation","tr":"Şaside, kabinde, bağlantı ayaklarında ve kaldırma veya çekme noktalarında çatlak, gevşemiş bağlantı veya deformasyon yok"},"response":"pass-fail-na","photo":"required-on-fail","refs":["tr-is-ekipmanlari","osha-co-alert"]},{"id":"fuel-leaks","text":{"en":"The fuel tank, cap and fuel lines are tight and do not leak; there is no spilled fuel on or under the generator","tr":"Yakıt deposu, kapağı ve yakıt hortumları sıkı ve sızdırmıyor; jeneratörün üzerinde veya altında dökülmüş yakıt yok"},"guidance":{"en":"Fuel spilled on hot engine parts can ignite. Clean up any spill before starting.","tr":"Sıcak motor parçalarına dökülen yakıt tutuşabilir. Çalıştırmadan önce döküntüyü temizleyin."},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["osha-co-alert","osha-1926-152","osha-fs-generators","tr-is-ekipmanlari"]},{"id":"guards","text":{"en":"Guards and covers over the fan, belt and other moving parts are in place, undamaged and firmly fixed","tr":"Fan, kayış ve diğer hareketli parçaların muhafazaları ve kapakları yerinde, hasarsız ve sağlam şekilde sabitlenmiş"},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["tr-is-ekipmanlari"]},{"id":"hot-parts","text":{"en":"The exhaust and other hot parts are shielded or placed so that nobody can touch them by accident, and nothing combustible rests against them","tr":"Egzoz ve diğer sıcak parçalar, kimsenin kazayla dokunamayacağı şekilde korunmuş veya konumlanmış; üzerlerine yanıcı bir şey dayanmıyor"},"guidance":{"en":"A generator stays hot for a long time after it has stopped.","tr":"Jeneratör durduktan sonra da uzun süre sıcak kalır."},"response":"pass-fail-na","refs":["tr-is-ekipmanlari","osha-fs-generators"]},{"id":"oil-coolant","text":{"en":"Engine oil, and coolant on liquid-cooled sets, are at the levels given in the manufacturer's manual","tr":"Motor yağı ve su soğutmalı jeneratörlerde soğutma suyu, kullanım kılavuzunda verilen seviyelerde"},"guidance":{"en":"Check with the engine stopped and cool, as the manual describes.","tr":"Motor dururken ve soğukken, kullanım kılavuzunda anlatıldığı şekilde bakın."},"response":"pass-fail-na","refs":["tr-is-ekipmanlari","osha-co-alert"]},{"id":"refuelling","text":{"en":"The generator is refuelled only with the engine stopped and cooled down","tr":"Yakıt ikmali yalnızca motor durdurulmuş ve soğumuşken yapılıyor"},"guidance":{"en":"Fill the tank before the shift so that it does not have to be topped up while hot.","tr":"Depoyu vardiyadan önce doldurun; böylece sıcakken yakıt eklemek gerekmez."},"response":"pass-fail-na","critical":true,"refs":["osha-fs-generators","osha-1926-152","hse-hsg141"]},{"id":"no-smoking","text":{"en":"Nobody smokes and there is no open flame where the generator is refuelled or fuel is kept","tr":"Yakıt ikmali yapılan ve yakıtın bulunduğu yerde sigara içilmiyor, açık alev yok"},"response":"pass-fail-na","refs":["osha-1926-152","osha-fs-generators"]},{"id":"fuel-containers","text":{"en":"Fuel is kept and carried only in approved containers made for fuel and marked with their contents","tr":"Yakıt yalnızca bu iş için üretilmiş, onaylı ve içeriği üzerinde yazılı kaplarda saklanıyor ve taşınıyor"},"response":"pass-fail-na","photo":"required-on-fail","refs":["osha-1926-152","osha-fs-generators"]},{"id":"extinguisher","text":{"en":"A fire extinguisher suitable for fuel and electrical fires is close to the generator and the refuelling point","tr":"Jeneratörün ve yakıt ikmal noktasının yakınında yakıt ve elektrik yangınına uygun bir yangın söndürücü var"},"guidance":{"en":"US construction rule for fuelling areas: rated at least 20-B:C and within 75 feet (about 23 m).","tr":"ABD'nin inşaat kuralı, yakıt ikmal alanları için en az 20-B:C sınıfı bir söndürücünün 75 fit (yaklaşık 23 m) içinde bulunmasını ister."},"response":"pass-fail-na","refs":["osha-1926-152","tr-is-ekipmanlari"]}]},{"id":"electrical","title":{"en":"Earthing, protection and cables (engine stopped)","tr":"Topraklama, koruma ve kablolar (motor dururken)"},"items":[{"id":"earthing","text":{"en":"The generator is earthed (grounded) as the manufacturer's instructions and the site's electrical design require; any earth conductor and rod connection is tight and undamaged","tr":"Jeneratör, kullanım kılavuzunun ve tesisat projesinin gerektirdiği şekilde topraklanmış; topraklama iletkeni ve çubuk bağlantısı varsa sıkı ve hasarsız"},"guidance":{"en":"OSHA lets the frame serve as the grounding electrode only when the generator supplies cord-and-plug equipment through its own receptacles and these are bonded to the frame. HSE says larger generators supplying a site should be earthed. If unsure, ask a competent electrician.","tr":"OSHA, şasinin topraklama elektrodu sayılmasına yalnızca jeneratör kendi prizlerinden fişli ekipmanı besliyorsa ve prizler şasiye bağlıysa izin verir. HSE, şantiyeyi besleyen büyük jeneratörlerin topraklanmasını ister. Emin değilseniz yetkili bir elektrikçiye sorun."},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["osha-1926-404","osha-fs-grounding","osha-fs-generators","hse-hsg141","tr-is-ekipmanlari"]},{"id":"no-backfeed","text":{"en":"The generator is not connected to the wiring of a building or cabin, unless through a transfer switch installed by a qualified electrician","tr":"Jeneratör bir binanın veya konteynerin tesisatına bağlı değil; bağlıysa yetkili bir elektrikçinin kurduğu transfer şalteri üzerinden bağlı"},"guidance":{"en":"A direct connection can energise the supply network and electrocute people working on it.","tr":"Doğrudan bağlantı şebekeye geri besleme yapar ve hatta çalışanları elektrik akımına kaptırabilir."},"response":"pass-fail-na","critical":true,"refs":["osha-fs-generators","osha-fs-grounding"]},{"id":"rcd-fitted","text":{"en":"The sockets or outgoing circuits in use are protected by an RCD (GFCI) where the rules for the site require it","tr":"Kullanılan prizler veya çıkış devreleri, işyeri için geçerli kuralların gerektirdiği yerde kaçak akım koruma cihazıyla (kaçak akım rölesi) korunuyor"},"guidance":{"en":"US construction: GFCI on 120 V single-phase 15 and 20 A receptacles, or an assured grounding program. HSE: RCD on each circuit where more than one earthed (Class I) item is supplied, and on the outgoing circuits of larger generators.","tr":"HSE: jeneratörden birden fazla topraklı (Sınıf I) ekipman besleniyorsa her devrede, büyük jeneratörlerde çıkış devrelerinde kaçak akım koruması bulunur. ABD inşaat kuralı: 120 V tek fazlı 15 ve 20 A prizlerde kaçak akım koruması veya güvenceli topraklama programı."},"response":"pass-fail-na","critical":true,"refs":["osha-1926-404","hse-hsg141","osha-fs-generators"]},{"id":"protection-not-bypassed","text":{"en":"No circuit breaker, fuse or RCD has been bypassed, bridged or disabled","tr":"Hiçbir şalter, sigorta veya kaçak akım rölesi köprülenmemiş ya da devre dışı bırakılmamış"},"guidance":{"en":"A device that keeps tripping points to a fault: have a competent person find it.","tr":"Sık sık atan koruma cihazı bir arızaya işaret eder: nedenini yetkili bir kişi bulmalı."},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["hse-hsg141","osha-fs-generators"]},{"id":"sockets-panel","text":{"en":"Sockets, switches and the control panel are undamaged and dry, their covers are in place, and no live part or burn mark can be seen","tr":"Prizler, şalterler ve kumanda panosu hasarsız ve kuru; kapakları yerinde, açıkta gerilimli parça veya yanık izi yok"},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["tr-is-ekipmanlari","hse-hsg107","hse-hsg141","osha-1926-405"]},{"id":"cables-condition","text":{"en":"Extension cables, plugs and connectors have no cuts, fraying, taped joints, cracked casings or bent or missing pins","tr":"Uzatma kablolarında, fişlerde ve bağlantı elemanlarında kesik, yıpranma, bantlı ek, çatlak gövde, eğilmiş veya eksik pim yok"},"guidance":{"en":"The outer sheath should be gripped where it enters the plug: no coloured inner cores showing.","tr":"Dış kılıf fişe girdiği yerde sıkıca tutulmuş olmalı: içteki renkli damarlar görünmemeli."},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["osha-1926-416","osha-1910-334","hse-hsg141","hse-hsg107","osha-fs-generators"]},{"id":"cables-type","text":{"en":"Extension cables are flexible, have an earth (grounding) conductor, and are rated for the load and for outdoor or site use","tr":"Uzatma kabloları bükülgen tipte, topraklama iletkenli, yüke ve açık hava veya şantiye kullanımına uygun"},"guidance":{"en":"US construction: three-wire cords designed for hard or extra-hard usage. HSE: twin and earth cable is not used as an extension cable.","tr":"ABD inşaat kuralı üç iletkenli, ağır hizmet tipi kablo ister. HSE, sabit tesisat kablosunun (twin and earth) uzatma kablosu olarak kullanılmamasını söyler."},"response":"pass-fail-na","refs":["osha-1926-405","osha-fs-grounding","osha-fs-generators","hse-hsg141"]},{"id":"cables-routing","text":{"en":"Cables are run where vehicles, sharp edges and doors cannot damage them, they do not lie in water, and they do not cross walkways as a trip hazard","tr":"Kablolar araçların, keskin kenarların ve kapıların zarar veremeyeceği yerden geçirilmiş; suyun içinde durmuyor ve yürüme yollarında takılma tehlikesi yaratmıyor"},"response":"pass-fail-na","refs":["osha-1926-405","osha-1926-416","hse-hsg141"]},{"id":"load","text":{"en":"The total connected load does not exceed the rated output on the generator's nameplate","tr":"Bağlı toplam yük, jeneratörün etiketindeki anma gücünü aşmıyor"},"guidance":{"en":"Overloading leads to overheating, which can start a fire.","tr":"Aşırı yük aşırı ısınmaya, o da yangına yol açabilir."},"response":"pass-fail-na","refs":["osha-fs-generators"]},{"id":"stop-control","text":{"en":"The stop control, the emergency stop where fitted, and the main breaker can be seen, identified and reached","tr":"Durdurma kumandası, varsa acil durdurma butonu ve ana şalter görülebiliyor, tanınabiliyor ve ulaşılabiliyor"},"response":"pass-fail-na","refs":["tr-is-ekipmanlari"]},{"id":"periodic-control","text":{"en":"The periodic control of the generator and of the earthing installation is in date, and the report is available","tr":"Jeneratörün ve topraklama tesisatının periyodik kontrolünün süresi geçmemiş; raporu mevcut"},"guidance":{"en":"Türkiye: at least once a year unless a standard sets another period. A mobile generator used off the premises carries its last report with it.","tr":"Standartlarda süre belirtilmemişse yılda bir (Ek-III Tablo-3). Seyyar jeneratör işletme dışında kullanılıyorsa son periyodik kontrol raporu ekipmanla birlikte bulundurulur (madde 7)."},"response":"pass-fail-na","refs":["tr-is-ekipmanlari"]}]},{"id":"running","title":{"en":"Running check (no load connected)","tr":"Çalışma kontrolü (yük bağlı değilken)"},"items":[{"id":"runs-normally","text":{"en":"The generator starts and runs without unusual noise, vibration, smoke or smell","tr":"Jeneratör olağan dışı ses, titreşim, duman veya koku olmadan çalışıyor"},"guidance":{"en":"Switch off electrical equipment that smells strange or starts to smoke, and do not use it.","tr":"Garip koku veren veya duman çıkaran elektrikli ekipmanı kapatın ve kullanmayın."},"response":"pass-fail-na","critical":true,"refs":["tr-is-ekipmanlari","osha-fs-generators"]},{"id":"indicators","text":{"en":"Where fitted, the voltage, frequency, oil pressure and temperature readings are in the manufacturer's normal range and no warning is showing","tr":"Varsa gerilim, frekans, yağ basıncı ve sıcaklık göstergeleri imalatçının verdiği normal aralıkta; uyarı lambası yanmıyor"},"response":"pass-fail-na","refs":["tr-is-ekipmanlari"]},{"id":"leaks-running","text":{"en":"No fuel, oil or coolant leaks while the engine runs, and exhaust gas escapes only from the exhaust outlet","tr":"Motor çalışırken yakıt, yağ veya soğutma suyu kaçağı yok; egzoz gazı yalnızca egzoz çıkışından atılıyor"},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["tr-is-ekipmanlari","osha-co-alert"]},{"id":"rcd-test","text":{"en":"Each RCD (GFCI) trips when its test button is pressed, and resets","tr":"Her kaçak akım rölesi test düğmesine basıldığında atıyor ve yeniden kuruluyor"},"guidance":{"en":"HSE recommends this check daily. An RCD that does not trip is a failed critical check.","tr":"HSE bu denemenin her gün yapılmasını önerir. Atmayan kaçak akım rölesi kritik bir uygunsuzluktur."},"response":"pass-fail-na","critical":true,"refs":["hse-hsg141","osha-fs-grounding"]},{"id":"stop-works","text":{"en":"The stop control, and the emergency stop where fitted, stops the generator","tr":"Durdurma kumandası ve varsa acil durdurma butonu jeneratörü durduruyor"},"response":"pass-fail-na","critical":true,"refs":["tr-is-ekipmanlari"]}]},{"id":"result","title":{"en":"Result","tr":"Sonuç"},"items":[{"id":"defects-reported","text":{"en":"Every defect found has been recorded and reported to the supervisor","tr":"Tespit edilen her uygunsuzluk kaydedildi ve amire bildirildi"},"response":"yes-no-na","refs":["tr-is-ekipmanlari","hse-hsg107","osha-fs-grounding"]},{"id":"out-of-service","text":{"en":"If a critical check failed, the generator is stopped, its loads are disconnected and it is tagged \"Do not use\" until it has been repaired","tr":"Kritik bir madde uygun değilse jeneratör durduruldu, yükleri ayrıldı ve onarılana kadar \"Kullanmayın\" etiketi asıldı"},"response":"yes-no-na","critical":true,"refs":["tr-is-ekipmanlari","osha-1910-334","osha-fs-grounding","hse-hsg141"]},{"id":"notes","text":{"en":"Notes and defects found","tr":"Notlar ve tespit edilen uygunsuzluklar"},"response":"text","required":false}]}],"signOff":[{"role":{"en":"Operator","tr":"Operatör"}},{"role":{"en":"Supervisor","tr":"Amir"}}],"references":[{"id":"tr-is-ekipmanlari","jurisdiction":"TR","title":"İş Ekipmanlarının Kullanımında Sağlık ve Güvenlik Şartları Yönetmeliği (Resmî Gazete, 25.04.2013)","url":"https://www.mevzuat.gov.tr/MevzuatMetin/yonetmelik/7.5.18318.pdf","note":{"en":"Article 7 (periodic control); Annex I 2.3, 2.4, 2.6, 2.8, 2.10, 2.14, 2.17 to 2.19 (stopping, fixing, guards, hot parts, energy isolation, fire, electricity); Annex II 2.5 (combustion-engine mobile equipment only with sufficient air); Annex III 1.2, 1.3 to 1.3.2 (maintenance, operator check before each start of work, defective equipment out of use), 1.9, 2.3 and Table 3 (generator and earthing installation, 1 year).","tr":"Madde 7 (periyodik kontrol); Ek-I 2.3, 2.4, 2.6, 2.8, 2.10, 2.14, 2.17 - 2.19 (durdurma, sabitleme, koruyucular, sıcak parçalar, enerjinin kesilmesi, yangın, elektrik); Ek-II 2.5 (içten yanmalı motorlu seyyar iş ekipmanı için yeterli hava); Ek-III 1.2, 1.3 - 1.3.2 (bakım, her çalışmaya başlamadan önce operatör kontrolü, kusurlu ekipmanın kullanım dışı bırakılması), 1.9, 2.3 ve Tablo-3 (jeneratör ve topraklama tesisatı, 1 yıl)."}},{"id":"osha-1926-404","jurisdiction":"US","title":"OSHA 29 CFR 1926.404, Wiring design and protection (construction)","url":"https://www.osha.gov/laws-regs/regulations/standardnumber/1926/1926.404","note":{"en":"(b)(1) ground-fault protection on construction sites and the exception for two-wire generators up to 5 kW; (f)(3) grounding of portable and vehicle-mounted generators. 29 CFR 1910.304(g)(3) has the same generator rule for general industry.","tr":"(b)(1) inşaat alanlarında kaçak akım koruması ve 5 kW'a kadar iki iletkenli jeneratörler için istisna; (f)(3) portatif ve araç üstü jeneratörlerin topraklanması. 29 CFR 1910.304(g)(3) aynı kuralı genel sanayi için verir."}},{"id":"osha-1926-405","jurisdiction":"US","title":"OSHA 29 CFR 1926.405, Wiring methods, components, and equipment for general use (construction)","url":"https://www.osha.gov/laws-regs/regulations/standardnumber/1926/1926.405","note":{"en":"(a)(2)(ii)(I) flexible cords protected from damage; (a)(2)(ii)(J) three-wire extension cords for hard or extra-hard usage; (e)(2) and (j)(2)(ii) switches and receptacles in wet locations.","tr":"(a)(2)(ii)(I) bükülgen kabloların hasardan korunması; (a)(2)(ii)(J) üç iletkenli, ağır hizmet tipi uzatma kabloları; (e)(2) ve (j)(2)(ii) ıslak yerlerdeki şalter ve prizler."}},{"id":"osha-1926-416","jurisdiction":"US","title":"OSHA 29 CFR 1926.416, General requirements (electrical safety-related work practices, construction)","url":"https://www.osha.gov/laws-regs/regulations/standardnumber/1926/1926.416","note":{"en":"(b)(2) walkways kept clear of cords; (e)(1) worn or frayed cords and cables not used.","tr":"(b)(2) yürüme yollarının kablolardan arındırılması; (e)(1) yıpranmış veya aşınmış kabloların kullanılmaması."}},{"id":"osha-1910-334","jurisdiction":"US","title":"OSHA 29 CFR 1910.334, Use of equipment (electrical safety-related work practices)","url":"https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.334","note":{"en":"(a)(2) visual inspection of cord- and plug-connected equipment and extension cords before use on any shift; defective items removed from service.","tr":"(a)(2) fişli ekipmanın ve uzatma kablolarının her vardiyada kullanımdan önce gözle muayenesi; kusurlu olanların kullanım dışı bırakılması."}},{"id":"osha-1926-152","jurisdiction":"US","title":"OSHA 29 CFR 1926.152, Flammable liquids (construction)","url":"https://www.osha.gov/laws-regs/regulations/standardnumber/1926/1926.152","note":{"en":"(a)(1) approved containers; (f)(2) leakage and spillage; (g)(8) no smoking or open flames in fuelling areas; (g)(10) motors shut off during fuelling; (g)(11) fire extinguisher at fuelling areas.","tr":"(a)(1) onaylı kaplar; (f)(2) sızıntı ve döküntü; (g)(8) yakıt ikmal alanında sigara ve açık alev yasağı; (g)(10) ikmal sırasında motorun kapatılması; (g)(11) ikmal alanında yangın söndürücü."}},{"id":"osha-fs-generators","jurisdiction":"US","title":"OSHA Fact Sheet, Using Portable Generators Safely (FS-3286)","url":"https://www.osha.gov/sites/default/files/publications/OSHA3286.pdf","note":{"en":"Shock and backfeed, cords, GFCIs, grounding, keeping the generator dry, carbon monoxide and placement, refuelling and fuel storage, noise. Informational: it sets no new requirements.","tr":"Elektrik çarpması ve geri besleme, kablolar, kaçak akım koruması, topraklama, jeneratörün kuru tutulması, karbonmonoksit ve yerleşim, yakıt ikmali ve depolama, gürültü. Bilgilendirme amaçlıdır; yeni yükümlülük getirmez."}},{"id":"osha-fs-grounding","jurisdiction":"US","title":"OSHA Fact Sheet, Grounding Requirements for Portable Generators","url":"https://www.osha.gov/sites/default/files/publications/GROUNDING_PORT_GENERATOR.pdf","note":{"en":"When the frame replaces a grounding electrode, transfer switches, cords with a grounding conductor, visual inspection before use and tagging defective equipment. Informational.","tr":"Şasinin topraklama elektrodu yerine geçtiği durumlar, transfer şalteri, topraklama iletkenli kablolar, kullanımdan önce gözle muayene ve kusurlu ekipmanın etiketlenmesi. Bilgilendirme amaçlıdır."}},{"id":"osha-co-alert","jurisdiction":"US","title":"OSHA Alert, Preventing Carbon Monoxide Poisoning While Working with Portable Generators (OSHA 4105, 2020)","url":"https://www.osha.gov/sites/default/files/publications/OSHA4105.pdf","note":{"en":"Inspect for damage or loose fuel lines, keep dry, never indoors or near doors, windows and ventilation shafts, 3 to 4 feet of clear space.","tr":"Hasar ve gevşek yakıt hortumu kontrolü, kuru tutma, kapalı alanda ve kapı, pencere, havalandırma bacası yakınında çalıştırmama, 3 - 4 fit boşluk."}},{"id":"hse-hsg141","jurisdiction":"UK","title":"HSE, Electrical safety on construction sites, HSG141 (second edition, 2023)","url":"https://www.hse.gov.uk/pubns/books/hsg141.htm","note":{"en":"Paragraphs 59, 62 to 64 (damaged equipment, cables, maintenance, RCDs never bypassed); 68, 70 and 71 (daily RCD test, user checks); 75 and 79 (IP rating, cable routes); 81 to 87 (generators: enclosed spaces, fuel, earthing, RCD protection). Guidance.","tr":"Paragraf 59, 62 - 64 (hasarlı ekipman, kablolar, bakım, kaçak akım rölesinin köprülenmemesi); 68, 70 ve 71 (günlük test düğmesi denemesi, kullanıcı kontrolleri); 75 ve 79 (IP sınıfı, kablo güzergâhı); 81 - 87 (jeneratörler: kapalı alan, yakıt, topraklama, kaçak akım koruması). Rehber niteliğindedir."}},{"id":"hse-hsg107","jurisdiction":"UK","title":"HSE, Maintaining portable electrical equipment, HSG107 (third edition, 2013)","url":"https://www.hse.gov.uk/pubns/books/hsg107.htm","note":{"en":"Paragraphs 38 and 39 (user checks on cables, plugs, sockets and extension leads; faults reported and equipment taken out of use). Used for the cables and connectors only; generators themselves are outside its scope.","tr":"Paragraf 38 ve 39 (kablo, fiş, priz ve uzatma kablolarında kullanıcı kontrolleri; arızanın bildirilmesi ve ekipmanın kullanım dışı bırakılması). Yalnızca kablo ve bağlantılar için kullanılmıştır; jeneratörlerin kendisi bu rehberin kapsamı dışındadır."}}],"relatedPosts":["electrical-safety-inspection-checklist","lockout-tagout-loto-guide","construction-site-safety-inspection"]}