{"$schema":"https://findrisk.net/checklists/schema.json","schemaVersion":1,"id":"emergency-lighting-inspection-checklist","version":1,"date":"2026-11-26T10:55:57+03:00","category":"emergency","industries":["general","manufacturing","warehouse-logistics","healthcare","hospitality","education","retail","office"],"frequency":"monthly","page":{"en":{"slug":"emergency-lighting-inspection-checklist","title":"Emergency Lighting Inspection Checklist: Monthly Test Form","description":"Free emergency lighting inspection checklist: monthly function test, exit signs, charge indicators, annual duration test and records, with OSHA and UK basis.","intro":"An **emergency lighting inspection checklist** is the routine test that shows the emergency luminaires and illuminated exit signs in one zone come on by themselves when the normal supply is cut, stay lit, and light the escape route, and that the yearly full-duration test and the test records are up to date. The person assigned to check fire safety equipment completes one form per floor or zone; a route whose emergency lighting fails needs temporary measures until it is repaired.\n\nIn the United States, OSHA 29 CFR 1910.37(a)(4) requires exit lighting to be in proper working order at all times, and 1910.37(b) requires exit routes to be adequately lighted and exit signs to be illuminated. OSHA sets no test interval; the routine comes from the fire code adopted where you are. The Kansas State Fire Marshal's log, for example, cites the International Fire Code and NFPA 101 section 7.9.3 and asks for a 30-second functional test every month and a 90-minute test every year. In Türkiye, Articles 70 to 73 of the Regulation on the Fire Protection of Buildings require emergency lighting that comes on automatically and runs for at least 60 minutes, or 120 minutes where the occupant load is over 200, and Article 84 requires it to be periodically checked, tested and maintained as the relevant standards set out; the regulation itself gives no interval. Government guidance for England lists a monthly function test and an annual full discharge test.\n\nThis form is the user test. It does not replace the annual check by a competent person, the periodic control of the electrical installation, or a lighting-level measurement. To decide where emergency lighting is needed, start with our [fire risk assessment guide](/blog/fire-risk-assessment-guide); for who does what during an evacuation, see the [emergency action plan guide](/blog/emergency-action-plan-guide).","howToUse":["Number every emergency luminaire and illuminated exit sign on a floor plan or list, and split the building into zones that one person can walk in a single test.","Pick a time when the lights will not be needed straight after the test, for example early in a working day, and tell the people in the area.","Walk the zone with the normal supply on: look for damaged or covered units, charge indicators and anything blocking the light or the signs.","Cut the supply to the emergency lighting with the test switch or key, or press each unit's test button, and walk the route again. Mark each check Pass, Fail or N/A and write down the number of every unit that fails.","Restore the supply, check that the units are charging again, and report every failed unit for repair the same day. Put temporary measures in place where an escape route is left without emergency lighting.","Write the date, the zone, the result and your name in the emergency lighting log, sign the form and keep it with the fire safety records."],"faqs":[{"question":"How often should emergency lighting be tested?","answer":"It depends on the code that applies to your building. The Kansas State Fire Marshal's log, which cites the International Fire Code and NFPA 101 section 7.9.3, asks for a 30-second functional test every month and a 90-minute test once a year. Government guidance for England lists a daily visual check of any central controls, a monthly function test and an annual full discharge test. The Turkish fire regulation requires periodic control, testing and maintenance as the relevant standards set out, without giving an interval of its own."},{"question":"Does OSHA require emergency lights to be tested monthly?","answer":"OSHA's exit route standard does not set a test interval. 29 CFR 1910.37(a)(4) requires safeguards such as exit lighting to be in proper working order at all times, and 1910.37(b) requires exit routes to be adequately lighted and exit signs to be illuminated to at least five foot-candles (54 lux). Under 1910.35, an employer who complies with the exit-route provisions of NFPA 101 or the International Fire Code (2009 editions) is deemed to comply with the OSHA exit route rules. Monthly and annual tests come from those fire codes as adopted by your state or city."},{"question":"What is the difference between a function test and a duration test?","answer":"A function test is short: you cut the normal supply for long enough to see that every lamp and sign lights. The guidance for England describes it as operating the test facility for a period sufficient to ensure that each emergency lamp illuminates. A duration test runs the lights on their batteries for the full rated time, which shows whether the batteries still hold their charge. The same guidance notes that batteries typically take 24 hours to recharge afterwards."},{"question":"How long must emergency lighting stay on?","answer":"In Türkiye, Article 72 of the Regulation on the Fire Protection of Buildings requires at least 60 minutes, and at least 120 minutes where the occupant load is over 200. The guidance for England says systems are designed to operate for between one and three hours. The Kansas State Fire Marshal's log sets the annual test at 90 minutes. Check the rated duration on the unit label or in the system design, and test against that."},{"question":"Who can carry out the monthly emergency lighting test?","answer":"The guidance for England says you should be able to carry out most of the routine tests yourself, and that the emergency lighting should be tested and maintained by a competent person every year. In Türkiye, the building owner, manager or the official they have delegated is responsible for periodic control, testing and maintenance, and the yearly periodic control of the electrical installation is done by authorised electrical engineers or technicians."}],"tags":["emergency lighting inspection","emergency light test","exit sign inspection","monthly inspection","OSHA 1910.37","fire safety"]},"tr":{"slug":"acil-aydinlatma-kontrol-formu","title":"Acil Aydınlatma Kontrol Formu: Aylık Test Listesi","description":"Ücretsiz acil aydınlatma kontrol formu: aylık fonksiyon testi, yönlendirme işaretleri, şarj göstergesi, yıllık süre testi; Yangın Yönetmeliği dayanağıyla.","intro":"**Acil aydınlatma kontrol formu**, bir bölgedeki acil durum aydınlatma armatürlerinin ve ışıklı yönlendirme işaretlerinin normal besleme kesildiğinde kendiliğinden devreye girdiğini, yanık kaldığını ve kaçış yolunu aydınlattığını; ayrıca yıllık süre testinin ve test kayıtlarının güncel olduğunu doğrulamak içindir. Formu yangın güvenliği ekipmanının kontrolüyle görevlendirilen kişi, her kat veya bölge için ayrı doldurur. Acil aydınlatması çalışmayan bir kaçış yolu için onarıma kadar geçici önlem alınır.\n\nBinaların Yangından Korunması Hakkında Yönetmelik'in 70 ila 73. maddeleri kaçış yollarının aydınlatılmasını, acil durum aydınlatmasının normal aydınlatma kesildiğinde otomatik devreye girmesini ve en az 60 dakika, kullanıcı yükü 200'den fazlaysa en az 120 dakika çalışmasını ister. 84. madde, acil aydınlatma ve yönlendirme sistemlerinin ilgili standartlarda belirtilen şekilde periyodik kontrole, teste ve bakıma tabi tutulmasını şart koşar; yönetmelik süre vermez. İşyeri Bina ve Eklentileri Yönetmeliği Ek-1 de aydınlatılması gereken kaçış yolları ve acil çıkışlarda ayrı bir enerji kaynağına bağlı acil aydınlatma sistemi bulundurulmasını ister. Mevzuatta aylık bir kullanıcı testi süresi yoktur; aylık fonksiyon testi yaygın uygulamadır ve İngiltere'deki resmî rehber ile ABD'deki yangın kodlarında bu şekilde yer alır. ABD'de OSHA 1910.37 çıkış aydınlatmasının her zaman çalışır durumda olmasını ister.\n\nBu form kullanıcı testi içindir; yetkili kişilerce yapılan elektrik tesisatı periyodik kontrolünün, yetkin kişinin yıllık kontrolünün ve aydınlık düzeyi ölçümünün yerine geçmez. Acil aydınlatmanın nerede gerektiğini belirlemek için [yangın risk değerlendirmesi rehberimize](/blog/fire-risk-assessment-guide), tahliyede kimin ne yapacağı için [acil durum eylem planı rehberimize](/blog/emergency-action-plan-guide) bakabilirsiniz.","howToUse":["Bütün acil aydınlatma armatürlerini ve ışıklı yönlendirme işaretlerini kat planında veya bir listede numaralandırın; binayı bir kişinin tek testte dolaşabileceği bölgelere ayırın.","Testi, ışıklara hemen ardından ihtiyaç duyulmayacak bir saatte, örneğin mesai başında yapın ve bölgedeki çalışanlara haber verin.","Önce besleme varken bölgeyi dolaşın: hasarlı veya üstü kapatılmış armatürlere, şarj göstergelerine ve ışığın ya da işaretlerin önünü kapatan şeylere bakın.","Test anahtarıyla acil aydınlatmanın beslemesini kesin veya her armatürün test düğmesine basın ve güzergâhı yeniden yürüyün. Her maddeyi Uygun, Uygun değil veya Kapsam dışı olarak işaretleyin, yanmayan her armatürün numarasını yazın.","Beslemeyi geri verin, armatürlerin yeniden şarja geçtiğini kontrol edin ve arızalı armatürleri aynı gün onarım için bildirin. Acil aydınlatmasız kalan kaçış yolu için geçici önlem alın.","Tarihi, bölgeyi, sonucu ve adınızı acil aydınlatma kayıt defterine yazın, formu imzalayın ve yangın güvenliği kayıtlarıyla birlikte saklayın."],"faqs":[{"question":"Acil aydınlatma armatürleri ne sıklıkla test edilir?","answer":"Binaların Yangından Korunması Hakkında Yönetmelik Madde 84, acil aydınlatma ve yönlendirme sistemlerinin ilgili standartlarda belirtilen şekilde periyodik kontrole, teste ve bakıma tabi tutulmasını ister; yönetmeliğin kendisi süre vermez. Elektrik tesisatının periyodik kontrolü, İş Ekipmanları Yönetmeliği Ek-III'e göre standartlarda süre belirtilmemişse yılda bir yapılır. Bu form, İngiltere'deki resmî rehberde ve ABD'deki yangın kodlarında olduğu gibi aylık kısa bir fonksiyon testini ve yılda bir tam süre testini esas alır."},{"question":"Acil aydınlatma kaç dakika yanmalı?","answer":"Yönetmeliğin 72. maddesine göre acil durum aydınlatması en az 60 dakika, kullanıcı yükü 200'den fazla olan yerlerde en az 120 dakika çalışmalıdır. Aynı madde kaçış yolunun ekseninde en az 1 lux aydınlık düzeyi ister; bu değer sürenin sonunda 0,5 lux'ün altına düşmemelidir. Yönlendirme işaretleri için de 73. maddede aynı süreler geçerlidir."},{"question":"Hangi yerlerde acil aydınlatma bulunmalı?","answer":"İşyeri Bina ve Eklentileri Yönetmeliği Ek-1'e göre aydınlatılması gereken kaçış yolları ve acil çıkışlarda, ayrıca aydınlatmanın kesilmesinin risk oluşturabileceği yerlerde ayrı bir enerji kaynağına bağlı acil aydınlatma sistemi bulundurulur. Binaların Yangından Korunması Hakkında Yönetmelik Madde 71 bütün kaçış yollarının ve kaçış merdivenlerinin aydınlatılmasını ister ve doğal aydınlatmayı yeterli kabul etmez; acil durum aydınlatmasının zorunlu olduğu yerler 72. maddede sayılır."},{"question":"Acil aydınlatma testini kim yapar?","answer":"Aylık fonksiyon testini görevlendirilmiş ve bilgilendirilmiş bir çalışan yapabilir. Sistemlerin periyodik kontrol, test ve bakımının yaptırılmasından bina sahibi, yöneticisi veya bunların yetki devrettiği bina yetkilisi sorumludur. Elektrik tesisatının yıllık periyodik kontrolünü, İş Ekipmanları Yönetmeliği Ek-III madde 2.3.2'de sayılan yetkili elektrik mühendisleri, teknikerleri ve diğer meslek mensupları yapar."},{"question":"Acil çıkış yönlendirme işaretleri nasıl olmalı?","answer":"Yönetmeliğin 73. maddesine göre birden fazla çıkışı olan binalarda acil durum yönlendirmesi yapılır. İşaretler yeşil zemin üzerine beyaz olur, normal çıkışlarda \"ÇIKIŞ\", acil çıkışlarda \"ACİL ÇIKIŞ\" yazar; işaret yüksekliği en az 15 cm'dir ve işaretler zeminden 200 ila 240 cm yüksekliğe yerleştirilir. İşaretler hem normal hem acil durum aydınlatmasında görülebilmeli, 60 dakika, kullanıcı yükü 200'den fazlaysa 120 dakika aydınlatılmalıdır."}],"tags":["acil aydınlatma kontrolü","acil aydınlatma kontrol formu","acil aydınlatma testi","yönlendirme işaretleri","aylık kontrol","yangın güvenliği"]}},"roles":{"completedBy":{"en":"Person assigned to check fire safety equipment","tr":"Yangın güvenliği ekipmanının kontrolüyle görevlendirilen kişi"},"approvedBy":{"en":"Facility manager","tr":"Bina / tesis yöneticisi"}},"header":[{"id":"site","label":{"en":"Site / building","tr":"İşyeri / bina"},"type":"text"},{"id":"zone","label":{"en":"Floor or zone tested","tr":"Test edilen kat veya bölge"},"type":"text"},{"id":"system-type","label":{"en":"System type","tr":"Sistem tipi"},"type":"select","options":[{"id":"self-contained","label":{"en":"Self-contained units (own battery)","tr":"Kendinden akülü armatürler"}},{"id":"central-battery","label":{"en":"Central battery system","tr":"Merkezi akülü sistem"}},{"id":"generator-backed","label":{"en":"Generator-backed","tr":"Jeneratör beslemeli"}},{"id":"mixed","label":{"en":"Mixed","tr":"Karma"}}]},{"id":"test-type","label":{"en":"Test type","tr":"Test türü"},"type":"select","options":[{"id":"function","label":{"en":"Monthly function test","tr":"Aylık fonksiyon testi"}},{"id":"duration","label":{"en":"Full-duration test","tr":"Tam süre testi"}}]},{"id":"unit-count","label":{"en":"Luminaires and exit signs in the zone","tr":"Bölgedeki armatür ve işaret sayısı"},"type":"number","required":false},{"id":"rated-duration","label":{"en":"Rated duration","tr":"Anma çalışma süresi"},"type":"number","unit":"min","required":false},{"id":"tested-at","label":{"en":"Date and time","tr":"Tarih ve saat"},"type":"datetime"}],"sections":[{"id":"before-test","title":{"en":"Before the test: normal supply on","tr":"Testten önce: besleme varken"},"items":[{"id":"register","text":{"en":"Every emergency luminaire and illuminated exit sign in the zone is numbered on a plan or list","tr":"Bölgedeki her acil aydınlatma armatürü ve ışıklı yönlendirme işareti planda veya listede numaralı"},"response":"yes-no-na","refs":["uk-fsra","ks-fire-fact-050"]},{"id":"units-undamaged","text":{"en":"Luminaires and exit signs are in place, undamaged and not painted over or covered","tr":"Armatürler ve yönlendirme işaretleri yerinde, hasarsız; üzeri boyanmamış veya kapatılmamış"},"guidance":{"en":"Look for cracked or missing diffusers, loose fittings, water marks and units left hanging by their cable.","tr":"Kırık veya eksik kapak, gevşek bağlantı, su izi ve kablosundan sarkan armatür olup olmadığına bakın."},"response":"pass-fail-na","photo":"required-on-fail","refs":["uk-fsra","osha-1910-37"]},{"id":"charge-indicators","text":{"en":"The charge indicator on each self-contained unit is visible and shows that the unit is charging","tr":"Kendinden akülü her armatürün şarj göstergesi görünüyor ve armatürün şarjda olduğunu gösteriyor"},"guidance":{"en":"The meaning of the indicator colours is on the unit label or in the maker's instructions. Mark N/A where no indicator is fitted.","tr":"Gösterge renklerinin anlamı armatür etiketinde veya üretici talimatında yazar. Gösterge yoksa Kapsam dışı işaretleyin."},"response":"pass-fail-na","photo":"required-on-fail","refs":["uk-fsra"]},{"id":"central-controls","text":{"en":"The central battery or control panel shows no fault","tr":"Merkezi akü veya kontrol panelinde arıza göstergesi yok"},"guidance":{"en":"Mark N/A for self-contained units without central controls.","tr":"Merkezi kumandası olmayan kendinden akülü armatürlerde Kapsam dışı işaretleyin."},"response":"pass-fail-na","photo":"required-on-fail","refs":["uk-fsra"]},{"id":"not-obstructed","text":{"en":"Nothing blocks the light from the luminaires or the view of the exit signs","tr":"Armatürlerin ışığını veya yönlendirme işaretlerinin görünmesini engelleyen bir şey yok"},"guidance":{"en":"Typical causes: high stock, new racking or partitions, banners, decorations, and other lit signs that confuse the direction of escape.","tr":"Sık görülenler: yüksek istif, sonradan kurulan raf veya bölme, afiş, süsleme ve kaçış yönünü karıştıran başka ışıklı tabelalar."},"response":"pass-fail-na","photo":"required-on-fail","refs":["osha-1910-37","bykhy"]},{"id":"signs-visible-normal","text":{"en":"Exit and direction signs are clearly visible and legible under normal lighting","tr":"Çıkış ve yönlendirme işaretleri normal aydınlatmada açıkça görülüyor ve okunuyor"},"response":"pass-fail-na","photo":"required-on-fail","refs":["bykhy","osha-1910-37"]},{"id":"test-timing","text":{"en":"The test is being done at a time when the lights will not be needed immediately afterwards","tr":"Test, ışıklara hemen ardından ihtiyaç duyulmayacak bir zamanda yapılıyor"},"response":"yes-no","refs":["uk-fsra"]}]},{"id":"function-test","title":{"en":"Function test: normal supply cut","tr":"Fonksiyon testi: besleme kesikken"},"description":{"en":"Use the test switch, key or each unit's test button. Do not isolate circuits you are not authorised to work on.","tr":"Test anahtarını veya her armatürün test düğmesini kullanın. Yetkiniz olmayan devrelerin enerjisini kesmeyin."},"items":[{"id":"auto-on","text":{"en":"The emergency lighting comes on automatically when the normal supply is cut","tr":"Normal besleme kesildiğinde acil durum aydınlatması kendiliğinden devreye giriyor"},"response":"pass-fail-na","critical":true,"refs":["bykhy","isyeri-bina","uk-fso"]},{"id":"all-lamps-lit","text":{"en":"Every emergency luminaire in the zone lights and stays lit for the whole test","tr":"Bölgedeki her acil aydınlatma armatürü yanıyor ve test boyunca yanık kalıyor"},"guidance":{"en":"England: long enough to make sure each emergency lamp illuminates. Kansas fire marshal's log (IFC, NFPA 101 section 7.9.3): 30 seconds every month. Write the number of each failed unit in the notes.","tr":"İngiltere rehberi: her lambanın yandığından emin olunacak kadar. ABD'de Kansas eyalet itfaiye formu: her ay 30 saniye. Yanmayan her armatürün numarasını notlara yazın."},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["uk-fsra","ks-fire-fact-050","bykhy"]},{"id":"exit-signs-lit","text":{"en":"Every exit and direction sign is lit and legible during the test","tr":"Her çıkış ve yönlendirme işareti test sırasında aydınlık ve okunaklı"},"response":"pass-fail-na","critical":true,"photo":"required-on-fail","refs":["bykhy","uk-fsra","ks-fire-fact-050","osha-1910-37"]},{"id":"brightness","text":{"en":"The lamps give a steady light, with no unit clearly dimmer than the others or flickering","tr":"Lambalar sabit ışık veriyor; diğerlerinden belirgin biçimde sönük veya titreyen armatür yok"},"response":"pass-fail-na","photo":"required-on-fail","refs":["uk-fsra"]},{"id":"route-coverage","text":{"en":"With the normal lighting off, exit doors, corridors and their intersections, stairs and changes in floor level are lit well enough to walk the route","tr":"Normal aydınlatma kapalıyken çıkış kapıları, koridorlar ve kesişimleri, merdivenler ve kot farkları güzergâhı yürümeye yetecek kadar aydınlık"},"guidance":{"en":"Türkiye: at least 1 lux on the centre line of the escape route. This form does not ask you to measure it; report dark stretches for assessment.","tr":"Yönetmelik kaçış yolu ekseninde en az 1 lux ister. Bu form ölçüm istemez; karanlık kalan kesimleri değerlendirilmek üzere bildirin."},"response":"pass-fail-na","photo":"required-on-fail","refs":["uk-fsra","bykhy"]},{"id":"equipment-points","text":{"en":"Fire alarm call points and firefighting equipment on the route can be seen in the emergency lighting","tr":"Güzergâhtaki yangın ihbar butonları ve söndürme ekipmanı acil aydınlatmada görülebiliyor"},"response":"pass-fail-na","refs":["uk-fsra"]},{"id":"outside-final-exit","text":{"en":"The area outside each final exit and any external escape route is lit","tr":"Her son çıkışın dışı ve varsa dış kaçış yolu aydınlık"},"guidance":{"en":"Mark N/A if the zone has no final exit.","tr":"Bölgede dışarıya açılan çıkış yoksa Kapsam dışı işaretleyin."},"response":"pass-fail-na","photo":"required-on-fail","refs":["uk-fsra"]},{"id":"generator","text":{"en":"Where a generator feeds the emergency lighting, it has been test-run this month","tr":"Acil aydınlatma jeneratörden besleniyorsa, jeneratör bu ay test amacıyla çalıştırıldı"},"guidance":{"en":"The England guide's example checklist: emergency generators tested monthly, normally run for one hour. Mark N/A if there is no generator.","tr":"İngiltere rehberindeki örnek liste: jeneratörler ayda bir test edilir, normalde bir saat çalıştırılır. Jeneratör yoksa Kapsam dışı işaretleyin."},"response":"yes-no-na","refs":["uk-fsra"]},{"id":"torches","text":{"en":"Safety torches kept for escape are in their places and work","tr":"Kaçış için bulundurulan el fenerleri yerinde ve çalışıyor"},"guidance":{"en":"Mark N/A if torches are not part of your arrangements.","tr":"El feneri düzenlemenizin parçası değilse Kapsam dışı işaretleyin."},"response":"pass-fail-na","refs":["uk-fsra"]}]},{"id":"after-test","title":{"en":"After the test","tr":"Testten sonra"},"items":[{"id":"supply-restored","text":{"en":"The normal supply is restored, the test switch is back in its normal position and the key is removed","tr":"Normal besleme geri verildi, test anahtarı normal konumuna alındı ve çıkarıldı"},"response":"yes-no","refs":["uk-fsra"]},{"id":"recharging","text":{"en":"The charge indicators show that the units are charging again","tr":"Şarj göstergeleri armatürlerin yeniden şarja geçtiğini gösteriyor"},"guidance":{"en":"Mark N/A where no indicator is fitted.","tr":"Gösterge yoksa Kapsam dışı işaretleyin."},"response":"pass-fail-na","refs":["uk-fsra"]}]},{"id":"duration-records","title":{"en":"Duration test, yearly check and earlier defects","tr":"Süre testi, yıllık kontrol ve önceki arızalar"},"items":[{"id":"duration-test-current","text":{"en":"The log shows a full-duration test of this zone within the last 12 months, and every unit lasted its rated time","tr":"Kayıtlar bu bölgede son 12 ay içinde tam süre testi yapıldığını ve her armatürün anma süresince yandığını gösteriyor"},"guidance":{"en":"Türkiye: at least 60 minutes, 120 minutes where the occupant load is over 200. England: annual full discharge test. Kansas fire marshal's log: 90 minutes every year.","tr":"Yönetmelik en az 60 dakika, kullanıcı yükü 200'den fazlaysa en az 120 dakika çalışma ister. İngiltere rehberi yılda bir tam deşarj testi önerir."},"response":"yes-no-na","refs":["bykhy","uk-fsra","ks-fire-fact-050"]},{"id":"reoccupation","text":{"en":"After a full-duration test, the area is not used in darkness until the batteries have recharged, unless other arrangements are in place","tr":"Tam süre testinden sonra, aküler yeniden dolana kadar alan karanlıkta kullanılmıyor veya başka bir düzenleme yapıldı"},"guidance":{"en":"The England guide notes that batteries typically take 24 hours to recharge. Mark N/A for a monthly function test.","tr":"İngiltere rehberi akülerin yeniden dolmasının genellikle 24 saat sürdüğünü belirtir. Aylık fonksiyon testinde Kapsam dışı işaretleyin."},"response":"yes-no-na","refs":["uk-fsra"]},{"id":"competent-check","text":{"en":"The records show that a competent person has tested and maintained the system within the last 12 months","tr":"Kayıtlar, sistemin son 12 ay içinde yetkin veya yetkili kişilerce test edildiğini, bakımının ve periyodik kontrolünün yapıldığını gösteriyor"},"guidance":{"en":"Türkiye: periodic control, testing and maintenance as the relevant standards set out; the electrical installation is periodically controlled at least yearly by authorised persons unless a standard gives another interval.","tr":"Yangın Yönetmeliği Madde 84: ilgili standartlara göre periyodik kontrol, test ve bakım. Elektrik tesisatının periyodik kontrolü, standartlarda süre belirtilmemişse en geç yılda bir yetkili kişilerce yapılır."},"response":"yes-no-na","refs":["uk-fsra","uk-fso","bykhy","is-ekipmanlari"]},{"id":"previous-defects","text":{"en":"Units that failed the previous test have been repaired or replaced","tr":"Önceki testte arızalı bulunan armatürler onarıldı veya değiştirildi"},"response":"yes-no-na","refs":["ks-fire-fact-050","osha-1910-37"]}]},{"id":"result","title":{"en":"Result","tr":"Sonuç"},"items":[{"id":"defects-reported","text":{"en":"Every failed unit has been reported, with its number, to the person responsible for the building's fire safety systems","tr":"Arızalı her armatür, numarasıyla birlikte binanın yangın güvenlik sistemlerinden sorumlu kişiye bildirildi"},"response":"yes-no-na","refs":["bykhy","ks-fire-fact-050"]},{"id":"temporary-measures","text":{"en":"If a critical check failed, temporary measures cover the affected escape route until the lighting is repaired","tr":"Kritik bir madde uygun değilse, aydınlatma onarılana kadar etkilenen kaçış yolu için geçici önlem alındı"},"guidance":{"en":"For example torches for trained staff, or not using the area in darkness.","tr":"Örneğin eğitimli çalışanlar için el feneri bulundurmak veya alanı karanlıkta kullanmamak."},"response":"yes-no-na","critical":true,"refs":["uk-fsra","osha-1910-37"]},{"id":"record-updated","text":{"en":"The date, zone, units tested, result and tester's name are entered in the emergency lighting log","tr":"Tarih, bölge, test edilen armatürler, sonuç ve testi yapanın adı acil aydınlatma kayıt defterine işlendi"},"response":"yes-no","refs":["uk-fsra","ks-fire-fact-050"]},{"id":"system-ready","text":{"en":"The emergency lighting in this zone is in working order","tr":"Bu bölgedeki acil aydınlatma çalışır durumda"},"response":"yes-no","critical":true,"refs":["osha-1910-37","isyeri-bina"]},{"id":"notes","text":{"en":"Notes and numbers of failed units","tr":"Notlar ve arızalı armatür numaraları"},"response":"text","required":false}]}],"signOff":[{"role":{"en":"Tester","tr":"Testi yapan"}},{"role":{"en":"Facility manager","tr":"Bina / tesis yöneticisi"}}],"references":[{"id":"bykhy","jurisdiction":"TR","title":"Binaların Yangından Korunması Hakkında Yönetmelik (Resmî Gazete, 19.12.2007, 26735)","url":"https://www.mevzuat.gov.tr/mevzuat?MevzuatNo=200712937&MevzuatTur=21&MevzuatTertip=5","note":{"en":"Article 70 (emergency lighting switches on automatically), 71 (all escape routes and stairs lit), 72 (automatic operation, at least 60 minutes or 120 minutes where the occupant load is over 200, at least 1 lux on the route centre line), 73 (direction signs: lit, duration, colours, size, height, visibility), 84 (periodic control, testing and maintenance of emergency lighting and direction systems as the relevant standards set out) and 67 (owner's or manager's responsibility).","tr":"Madde 70 (acil durum aydınlatmasının otomatik devreye girmesi), 71 (bütün kaçış yolları ve merdivenlerinin aydınlatılması), 72 (otomatik çalışma, en az 60 dakika, kullanıcı yükü 200'den fazlaysa 120 dakika, kaçış yolu ekseninde en az 1 lux), 73 (yönlendirme işaretleri: aydınlatma, süre, renk, boyut, yükseklik, görünürlük), 84 (acil aydınlatma ve yönlendirme sistemlerinin ilgili standartlara göre periyodik kontrol, test ve bakımı) ve 67 (bina sahibi veya yöneticisinin sorumluluğu)."}},{"id":"isyeri-bina","jurisdiction":"TR","title":"İşyeri Bina ve Eklentilerinde Alınacak Sağlık ve Güvenlik Önlemlerine İlişkin Yönetmelik (Resmî Gazete, 17.07.2013, 28710)","url":"https://www.resmigazete.gov.tr/eskiler/2013/07/20130717-2.htm","note":{"en":"Annex 1, item 10(e) and (f) (marking of escape routes and exits; emergency lighting on a separate energy source where they need lighting) and item 24 (emergency lighting where a lighting failure could create a risk).","tr":"Ek-1 md. 10(e) ve (f) (kaçış yolları ve çıkışların işaretlenmesi; aydınlatılması gereken yerlerde ayrı bir enerji kaynağına bağlı acil aydınlatma) ve md. 24 (aydınlatmanın kesilmesinin risk oluşturabileceği yerlerde acil aydınlatma)."}},{"id":"is-ekipmanlari","jurisdiction":"TR","title":"İş Ekipmanlarının Kullanımında Sağlık ve Güvenlik Şartları Yönetmeliği (Resmî Gazete, 25.04.2013, 28628)","url":"https://www.mevzuat.gov.tr/MevzuatMetin/yonetmelik/7.5.18318.pdf","note":{"en":"Annex III, 2.3.1 (installations: periodic control yearly unless standards say otherwise), 2.3.2 (persons authorised to control electrical installations) and Table 3 (electrical installation: one year unless a standard gives an interval).","tr":"Ek-III md. 2.3.1 (tesisatların periyodik kontrolü, standartlarda aksi belirtilmedikçe yılda bir), 2.3.2 (elektrik tesisatının periyodik kontrolünü yapmaya yetkili kişiler) ve Tablo-3 (elektrik tesisatı: standartlarda süre belirtilmemişse 1 yıl)."}},{"id":"osha-1910-37","jurisdiction":"US","title":"OSHA 29 CFR 1910.37, Maintenance, safeguards, and operational features for exit routes","url":"https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.37","note":{"en":"(a)(4) safeguards such as exit lighting in proper working order at all times; (b)(1) exit routes adequately lighted; (b)(2)–(b)(4) exits marked, signs not obscured, line of sight to exit signs; (b)(6) exit signs illuminated to at least five foot-candles (54 lux). The section sets no test interval.","tr":"(a)(4) çıkış aydınlatması gibi önlemlerin her zaman çalışır durumda olması; (b)(1) çıkış yollarının yeterince aydınlatılması; (b)(2)–(b)(4) çıkışların işaretlenmesi, işaretlerin kapatılmaması, işaretlerin görüş hattı; (b)(6) çıkış işaretlerinin en az 54 lux ile aydınlatılması. Madde test süresi vermez."}},{"id":"osha-1910-35","jurisdiction":"US","title":"OSHA 29 CFR 1910.35, Compliance with alternate exit-route codes","url":"https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.35","note":{"en":"Compliance with the exit-route provisions of NFPA 101 (2009 edition) or the International Fire Code (2009 edition) is deemed compliance with 1910.34, 1910.36 and 1910.37. Used in the introduction and FAQs.","tr":"NFPA 101 (2009) veya International Fire Code (2009) çıkış yolu hükümlerine uyum, 1910.34, 1910.36 ve 1910.37'ye uyum sayılır. Giriş metninde ve SSS'de kullanılmıştır."}},{"id":"ks-fire-fact-050","jurisdiction":"US","title":"Kansas Office of the State Fire Marshal, Fire Fact 050: Emergency Lights/Signs Log","url":"https://www.firemarshal.ks.gov/DocumentCenter/View/395/Fire-Fact-050---Emergency-Lighting-Log-PDF","note":{"en":"State example of the fire-code routine, citing the International Fire Code and NFPA 101 section 7.9.3: 30-second functional test every month, 90-minute test every year, a dated and initialled entry for each unit, comments on failure and replacement, documentation kept.","tr":"Yangın kodu uygulamasına eyalet örneği (International Fire Code ve NFPA 101 bölüm 7.9.3'e atıfla): her ay 30 saniyelik fonksiyon testi, yılda bir 90 dakikalık test, her armatür için tarihli ve paraflı kayıt, arıza ve değişim notları, kayıtların saklanması."}},{"id":"uk-fsra","jurisdiction":"UK","title":"HM Government, Fire safety risk assessment: offices and shops (updated 12 September 2023)","url":"https://www.gov.uk/government/publications/fire-safety-risk-assessment-offices-and-shops/fire-safety-risk-assessment-offices-and-shops-accessible","note":{"en":"Part 1, 3.4.4 (when emergency escape lighting is needed, torches) and 3.4.6 (daily, monthly and annual checks); Part 2, Section 5 (what the lighting should cover, function test, annual full discharge test, recharge time, records; names BS 5266-1 and BS 5266-8 for further guidance); 7.1 (records and plans); Appendix A1 (example checklist). Guidance for England under the Regulatory Reform (Fire Safety) Order 2005.","tr":"Bölüm 1, 3.4.4 (acil kaçış aydınlatmasının ne zaman gerektiği, el fenerleri) ve 3.4.6 (günlük, aylık ve yıllık kontroller); Bölüm 2, Kısım 5 (aydınlatmanın kapsaması gereken noktalar, fonksiyon testi, yıllık tam deşarj testi, yeniden şarj süresi, kayıt); 7.1 (kayıtlar ve planlar); Ek A1 (örnek kontrol listesi). İngiltere için rehber niteliğindedir."}},{"id":"uk-fso","jurisdiction":"UK","title":"The Regulatory Reform (Fire Safety) Order 2005 (S.I. 2005/1541)","url":"https://www.legislation.gov.uk/uksi/2005/1541/article/14","note":{"en":"Article 14(2)(h) (emergency lighting of adequate intensity on routes and exits that need illumination, in case the normal lighting fails) and Article 17(1) (suitable system of maintenance; efficient working order and good repair).","tr":"Madde 14(2)(h) (aydınlatma gerektiren kaçış yolları ve çıkışlarda, normal aydınlatmanın kesilmesi hâli için yeterli şiddette acil aydınlatma) ve Madde 17(1) (uygun bakım sistemi; etkin çalışır durumda tutma)."}}],"relatedPosts":["fire-risk-assessment-guide","emergency-action-plan-guide"]}